Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 1, 2020, 04:53 AM
  • 08 0482_08 0481A_08312020_220102.mp4

Date
08/31/2020
W/O
844358
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00007
PipeID
P23409
Time
9:53 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8012
Sewer Name
FRAMPTON AVENUE TRUNK
City
HARBOR CITY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
16
Purpose
Routine Assessment
Project
WO_844358_TV08086_AUG2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
08 0482
Downstream MH
08 0481A
Dir. of Survey
Downstream
Length Surveyed
155.8 ft.
Total Length
155.8 ft.
Structural Index
3
Structural Quick
3222
Structural Rating
10
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole 08 0482 to 08 0481A
MH: 08 0482MH: 08 0481Adownstream0 ft. AMH - Upstream Manhole, Survey Begins - 08 04820 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 5 %of cross sectional area4 ft. CM - Crack Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES9.7 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES40.3 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES47 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"89 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES97 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"147.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"155.8 ft. MGO - General Observation - CONNECTION IN MH, 3 O' CLOCK155.8 ft. AMH - Downstream Manhole, Survey Ends - 08 0481A

Observation photos (4)

  • Crack Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES

    4 ft. - Crack Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    9.7 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    40.3 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    89 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (12)

DistanceCodeObservation
155.8MGOCONNECTION IN MH, 3 O' CLOCK
47TFC
0AMH08 0482
0MWL
40.3CL
0MWM
147.1TFC
155.8AMH08 0481A
97TFC
9.7CL
4CM
89CM

Properties (7)

additional_info
SC411825
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2020-08-31T21:53:22-07:00
documentation
PROPIPE
is_lateral_inspection
false