Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 1, 2020, 04:26 AM
  • 08 0483_08 0482_08312020_214723.mp4

Date
08/31/2020
W/O
844358
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00007
PipeID
P00541
Time
9:26 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8012
Sewer Name
FRAMPTON AVENUE TRUNK
City
HARBOR CITY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
16
Purpose
Routine Assessment
Project
WO_844358_TV08086_AUG2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
36 in.
Upstream MH
08 0482
Downstream MH
08 0483
Dir. of Survey
Upstream
Length Surveyed
484.6 ft.
Total Length
484.6 ft.
Structural Index
2
Structural Quick
3223
Structural Rating
12
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
12
Pipe schematic from manhole 08 0482 to 08 0483
MH: 08 0482MH: 08 0483upstream0 ft. AMH - Upstream Manhole, Survey Ends - 08 04834.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"5.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"36.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"85.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"136.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"185.1 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES186.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"215.3 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES236.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"287.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"336.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"360.6 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES387.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"437.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"476.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES480.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES484.6 ft. MWL - Water Level, 5 %of cross sectional area484.6 ft. MWM - Water Mark, 5 %of cross sectional area484.6 ft. AMH - Downstream Manhole, Survey Begins - 08 0482

Observation photos (4)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    3.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    8.4 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    269.3 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    299.5 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

Observations (20)

DistanceCodeObservation
0MWL
347.9TFC
0MWM
124CL
298TFC
8.4FL
97.4TFC
484.6AMH08 0483
479.2TF
269.3CL
3.9CM
47.4TFC
247.8TFC
398.7TFC
299.5CL
197.4TFC
0AMH08 0482
479.7TF
448.3TF
147.7TF

Properties (7)

additional_info
SC411825
custom_field_three
no severe defects
custom_field_two
4
customer
1
datetime
2020-08-31T21:26:46-07:00
documentation
PROPIPE
is_lateral_inspection
false