Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 1, 2020, 05:01 AM
  • 08 0481A_08 0481_08312020_221700.mp4

Date
08/31/2020
W/O
844358
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00007
PipeID
P00540
Time
10:01 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8012
Sewer Name
FRAMPTON AVENUE TRUNK
City
HARBOR CITY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
16
Purpose
Routine Assessment
Project
WO_844358_TV08086_AUG2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
36 in.
Upstream MH
08 0481A
Downstream MH
08 0481
Dir. of Survey
Downstream
Length Surveyed
328.8 ft.
Total Length
328.8 ft.
Structural Index
3
Structural Quick
3H25
Structural Rating
148
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
148
Pipe schematic from manhole 08 0481A to 08 0481
MH: 08 0481AMH: 08 0481downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MGO - General Observation - CONNECTION IN MH, 3 O' CLOCK0 ft. MWM - Water Mark, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 0481A29 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES33.9 ft. CS - Crack Spiral, from 03 to 05 o'clock, within 8 inches of joint: YES41.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"44.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES64.8 ft. CM - Crack Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES70.5 ft. CS - Crack Spiral, from 07 to 10 o'clock, within 8 inches of joint: YES91.2 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES93.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"96.3 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES106.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start143.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"193.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"243.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"293.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"324.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish328.3 ft. MGO - General Observation - CONNECTION IN MH, 9 O' CLOCK328.8 ft. MGO - General Observation - CONNECTION IN MH, 3 O' CLOCK CAPPED328.8 ft. AMH - Downstream Manhole, Survey Ends - 08 0481

Observation photos (8)

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    29 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 03 to 05 o'clock, within 8 inches of joint: YES

    33.9 ft. - Crack Spiral, from 03 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    44.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES

    64.8 ft. - Crack Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 07 to 10 o'clock, within 8 inches of joint: YES

    70.5 ft. - Crack Spiral, from 07 to 10 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    91.2 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    96.3 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    106.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (22)

DistanceCodeObservation
293.8TF
44.3CM
96.3CL
106.3CM
93.5TFC
41.5TF
328.8MGOCONNECTION IN MH, 3 O' CLOCK CAPPED
29CL
328.8AMH08 0481
243.7TFC
0MWL
0MGOCONNECTION IN MH, 3 O' CLOCK
193.6TFC
70.5CS
0MWM
328.3MGOCONNECTION IN MH, 9 O' CLOCK
64.8CM
324.5CM
33.9CS
143.5TF
91.2CL
0AMH08 0481A

Properties (7)

additional_info
SC411825
custom_field_three
MULTIPLE CRACKS
custom_field_two
2
customer
1
datetime
2020-08-31T22:01:44-07:00
documentation
PROPIPE
is_lateral_inspection
false