Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 1, 2020, 06:19 AM
  • 08 0479_08 0478_08312020_232556.mp4

Date
08/31/2020
W/O
844358
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00007
PipeID
P00537
Time
11:19 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8012
Sewer Name
FRAMPTON AVENUE TRUNK
City
HARBOR CITY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
16
Purpose
Routine Assessment
Project
WO_844358_TV08086_AUG2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
36 in.
Upstream MH
08 0479
Downstream MH
08 0478
Dir. of Survey
Downstream
Length Surveyed
99.6 ft.
Total Length
99.6 ft.
Structural Index
3
Structural Quick
413B
Structural Rating
55
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
55
Pipe schematic from manhole 08 0479 to 08 0478
MH: 08 0479MH: 08 0478downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 04790 ft. MWM - Water Mark, 5 %of cross sectional area5 ft. FM - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES12.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start34.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"84.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"99.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish99.6 ft. MGO - General Observation - CONNECTION IN MH, 9 O' CLOCK CAPPED99.6 ft. AMH - Downstream Manhole, Survey Ends - 08 0478

Observation photos (2)

  • Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

    5 ft. - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    12.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
34.4TFC
99.6CM
0MWL
99.6MGOCONNECTION IN MH, 9 O' CLOCK CAPPED
99.6AMH08 0478
0AMH08 0479
0MWM
84.5TFC
5FM
12.5CM

Properties (7)

additional_info
SC411825
custom_field_three
MULTIPLE FRACTURES
custom_field_two
2
customer
1
datetime
2020-08-31T23:19:57-07:00
documentation
PROPIPE
is_lateral_inspection
false