Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 8, 2020, 05:12 PM
  • 29 0099_29 0083_09082020_103142.mp4

Date
09/08/2020
W/O
844696
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00273
PipeID
P23882
Time
10:12 AM
Certificate
U-109-7948
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7336
Sewer Name
33RD STREET SEWER
City
SIGNAL HILL
Loc. details
Alley
Location Code
H
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
01
Purpose
Routine Assessment
Project
RFIR_WO_844696_TV29102_AUG2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0099
Downstream MH
29 0083
Dir. of Survey
Downstream
Length Surveyed
253.1 ft.
Total Length
253.1 ft.
Structural Index
4
Structural Quick
4100
Structural Rating
4
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
6
Pipe schematic from manhole 29 0099 to 29 0083
MH: 29 0099MH: 29 0083downstream0 ft. AMH - Upstream Manhole, Survey Begins - 29 00990 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MH0 ft. MWL - Water Level, 5 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start20 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start24.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"30.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"32.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"79.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"107.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4" - ROOTS128.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"154.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"176.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4" - ROOTS181.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4" - ROOTS249.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish249.8 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish253.1 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK253.1 ft. AMH - Downstream Manhole, Survey Ends - 29 0083253.1 ft. MGO - General Observation - CONNECTION AT MH 12 O'CLOCK

Observation photos (4)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    20 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4" - ROOTS

    107.8 ft. - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4" - ROOTS

  • Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4" - ROOTS

    176.9 ft. - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4" - ROOTS

  • Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4" - ROOTS

    181.8 ft. - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4" - ROOTS

Observations (20)

DistanceCodeObservation
253.1MGOCONNECTION AT MH 3 O'CLOCK
2DAGS
249.8DAGS
79.9TFC
253.1AMH29 0083
0AMH29 0099
128.8TF
20FM
154.8TF
32.5TF
249.8FM
0MWM
0MGOCOCKROACHES IN MH
30.1TF
24.4TF
0MWL
253.1MGOCONNECTION AT MH 12 O'CLOCK
176.9TFAROOTS
181.8TFROOTS
107.8TFROOTS

Properties (7)

additional_info
SC411334
custom_field_three
MULTIPLE FRACTURES
custom_field_two
3
customer
1
datetime
2020-09-08T10:12:59-07:00
documentation
PRO PIPE
is_lateral_inspection
false