Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 17, 2020, 08:03 AM
  • C 0088_C 0086_09172020_Manual.mp4

Date
09/17/2020
W/O
0834128
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00122
PipeID
P09554
Time
1:03 AM
Certificate
U-1014-06022543
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0344
Sewer Name
JOINT OUTFALL C - UNIT 3C
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
23
Purpose
Capital Improvement Program Assesment
Project
20200916MDM_JOINT_OUTFALL_C_UNIT_3C
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
60 in.
Upstream MH
C 0088
Downstream MH
C 0086
Dir. of Survey
Downstream
Length Surveyed
1562.6 ft.
Total Length
1562.6 ft.
Structural Index
2
Structural Quick
513f
Structural Rating
1216
O&M Index
2
O&M Quick
2300
O&M Rating
6
Overall Index
2
Overall Quick
Overall Rating
1222
Pipe schematic from manhole C 0088 to C 0086
MH: C 0088MH: C 0086downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - MAG COAT 80% START 9:00 TO 3:000 ft. AMH - Upstream Manhole, Survey Begins - 1:55AM0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE37.9 ft. SAV - Surface Aggregate Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC134.1 ft. SAV - Surface Aggregate Visible, from 01 to 02 o'clock, within 8 inches of joint: NO - SEVERE AG VERY SPORATIC176.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - BLISTERING PEELING CONCRETE299.8 ft. IW - Infiltration Weeper, at 09 o'clock, within 8 inches of joint: YES308.4 ft. IW - Infiltration Weeper, from 09 to 12 o'clock, within 8 inches of joint: YES403.8 ft. IW - Infiltration Weeper, from 09 to 12 o'clock, within 8 inches of joint: YES - 3 JOINTS410.6 ft. MGO - General Observation - START 2ND TAPE SECTION594.8 ft. SAV - Surface Aggregate Visible, from 01 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG VERY SPORATIC594.8 ft. MGO - General Observation - 2ND ANGLE POINT614 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC681.1 ft. SAV - Surface Aggregate Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG1200.1 ft. SAV - Surface Aggregate Visible, from 02 to 03 o'clock, within 8 inches of joint: YES - SEVERE AGG1354 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES - CIRCUM REBAR1562.2 ft. MGO - General Observation - DEBRIE ON CABLE1562.2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG SPORATIC1562.2 ft. MGO - General Observation - 80% MAG FINISH1562.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE1562.6 ft. AMH - Downstream Manhole, Survey Ends - 4:25AM

Observations (23)

DistanceCodeObservation
299.8IW
0MWL
594.8SAVSEVERE AGG VERY SPORATIC
1562.2MGODEBRIE ON CABLE
1562.2SAVSEVERE AGG SPORATIC
134.1SAVSEVERE AG VERY SPORATIC
1562.2MGO80% MAG FINISH
1354SRVCIRCUM REBAR
410.6MGOSTART 2ND TAPE SECTION
1200.1SAVSEVERE AGG
1562.6AMH4:25AM
37.9SAVSEVERE AGG SPORATIC
0MGOMAG COAT 80% START 9:00 TO 3:00
2SSSBLISTERING PEELING CONCRETE
1562.2SSSBLISTERING PEELING CONCRETE
614SAVSEVERE AGG SPORATIC
403.8IW3 JOINTS
0AMH1:55AM
176.3SSSBLISTERING PEELING CONCRETE
0MWM
594.8MGO2ND ANGLE POINT
308.4IW
681.1SAVSEVERE AGG

Properties (6)

custom_field_three
CIRCUM REBAR VISIBLE 1 AREA-SEVERE AGG VISIBLE
custom_field_two
2
customer
1
datetime
2020-09-17T01:03:54-07:00
documentation
MARTIN,OLIVER 111,BARR,CASTILLO
is_lateral_inspection
false