Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 21, 2020, 10:36 AM
  • 02 1143_02 1142_9212020_034355.mp4

Date
09/21/2020
W/O
0849658
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00351
PipeID
P02927
Time
3:36 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1568
Sewer Name
02 GARFIELD AVENUE EXTENSION TRUNK
City
MONTEBELLO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
13
Purpose
Maintenance Related
Project
20200921MDM_GARFIELD_AVENUE_EXTENSION_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
02 1143
Downstream MH
02 1142
Dir. of Survey
Downstream
Length Surveyed
314.5 ft.
Total Length
314.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
1
O&M Quick
2117
O&M Rating
9
Overall Index
1
Overall Quick
Overall Rating
9
Pipe schematic from manhole 02 1143 to 02 1142
MH: 02 1143MH: 02 1142downstream0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0 ft. AMH - Upstream Manhole, Survey Begins - 3:40AM0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Capped0 ft. MWL - Water Level, 10 %of cross sectional area157.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped-70% ROOTS192 ft. RFJ - Roots Fine Joint, from 08 to 10 o'clock, within 8 inches of joint: YESR - 3%203.2 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR - 3%205.4 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open-100% ROOTS216.4 ft. RFJ - Roots Fine Joint, from 08 to 10 o'clock, within 8 inches of joint: YESR - 3%227.9 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR - 3%231.9 ft. RFJ - Roots Fine Joint, from 02 to 04 o'clock, within 8 inches of joint: YESR - 3%244 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR - 3%257.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped-50% ROOTS271.6 ft. RFJ - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YESR - 2%309.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped-50% ROOTS314.5 ft. AMH - Downstream Manhole, Survey Ends - 4:00AM

Observations (17)

DistanceCodeObservation
205.4TFDOpen-100% ROOTS
203.2RFJ3%
271.6RFJ2%
0MGOConn. @ Mh, 9 O' Clock. Active
257.7TFCCapped-50% ROOTS
227.9RFJ3%
244RFJ3%
309.2TFCCapped-50% ROOTS
157.5TFCCapped-70% ROOTS
231.9RFJ3%
0AMH3:40AM
0MWM
192RFJ3%
314.5AMH4:00AM
0MGOConn. @ Mh, 3 O' Clock. Capped
0MWL
216.4RFJ3%

Properties (4)

customer
LACSD
datetime
2020-09-21T03:36:33-07:00
documentation
MARTIN,OLIVER 111,CASTILLO
is_lateral_inspection
false