Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 15, 2020, 08:33 AM
  • C 0089_C 0088_9152020_014424.mp4

Date
09/15/2020
W/O
0834128
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00122
PipeID
P09554
Time
1:33 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1566
Sewer Name
C JOINT OUTFALL C - UNIT 3C
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
23
Purpose
Capital Improvement Program Assesment
Project
20200915MDM_JOINT_OUTFALL_C_UNIT_3C
Material
Reinforced Concrete Pipe
Shape
Circular
Height
60 in.
Upstream MH
C 0089
Downstream MH
C 0088
Dir. of Survey
Downstream
Length Surveyed
1190.8 ft.
Total Length
1190.8 ft.
Structural Index
3
Structural Quick
3524
Structural Rating
23
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
23
Pipe schematic from manhole C 0089 to C 0088
MH: C 0089MH: C 0088downstream0 ft. AMH - Upstream Manhole, Survey Begins - 1:55AM0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE2 ft. MGO - General Observation - MAG COAT 80% START 9:00 TO 3:0015.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, - BLISTERING PEELING CONCRETE66.4 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE124.1 ft. SAV - Surface Aggregate Visible, from 01 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC205.8 ft. SAV - Surface Aggregate Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC210.3 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start - VERY SEVERE AGG SPORATIC247.6 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG VERY SPORATIC831.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE UNDER MAG COAT962.9 ft. MGO - General Observation - 70% MAG COAT START986.6 ft. SAV - Surface Aggregate Visible, from 09 to 11 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC1190.3 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Finish - SEVERE AGG VERY SPORATIC1190.3 ft. MGO - General Observation - 70% MAG COAT FINISH1190.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE1190.3 ft. MGO - General Observation - DEBRIE ON CABLE1190.8 ft. AMH - Downstream Manhole, Survey Ends - 3:35AM

Observation photos (8)

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

    66.4 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

  • Surface Aggregate Visible, from 01 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

    124.1 ft. - Surface Aggregate Visible, from 01 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start - VERY SEVERE AGG SPORATIC

    210.3 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start - VERY SEVERE AGG SPORATIC

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG VERY SPORATIC

    247.6 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG VERY SPORATIC

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE UNDER MAG COAT

    831.8 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE UNDER MAG COAT

  • General Observation - 70% MAG COAT START

    962.9 ft. - General Observation - 70% MAG COAT START

  • Surface Aggregate Visible, from 09 to 11 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

    986.6 ft. - Surface Aggregate Visible, from 09 to 11 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

  • General Observation - DEBRIE ON CABLE

    1190.3 ft. - General Observation - DEBRIE ON CABLE

Observations (19)

DistanceCodeObservation
962.9MGO70% MAG COAT START
205.8SAVSEVERE AGG SPORATIC
2SSSBLISTERING PEELING CONCRETE
66.4SSSBLISTERING PEELING CONCRETE
1190.3SAVSEVERE AGG VERY SPORATIC
247.6SAVSEVERE AGG VERY SPORATIC
2MGOMAG COAT 80% START 9:00 TO 3:00
0AMH1:55AM
0MWL
1190.8AMH3:35AM
210.3SAVVERY SEVERE AGG SPORATIC
831.8SSSBLISTERING PEELING CONCRETE UNDER MAG COAT
986.6SAVSEVERE AGG SPORATIC
1190.3MGO70% MAG COAT FINISH
124.1SAVSEVERE AGG SPORATIC
1190.3SSSBLISTERING PEELING CONCRETE
15.5SSSBLISTERING PEELING CONCRETE
0MWM
1190.3MGODEBRIE ON CABLE

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2020-09-15T01:33:30-07:00
documentation
MARTIN,OLIVER 111,BARR,CASTILLO
is_lateral_inspection
false