Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 3, 2020, 04:34 AM
  • 08 0340_08 0339_09022020_214604.mp4

Date
09/02/2020
W/O
844356
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00003
PipeID
P00390
Time
9:34 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8019
Sewer Name
DAVIDSON CITY TRUNK, SECTS 1,2,&3
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
14
Purpose
Routine Assessment
Project
WO_844356_TV08012_AUG2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
12 in.
Upstream MH
08 0340
Downstream MH
08 0339
Dir. of Survey
Downstream
Length Surveyed
347.5 ft.
Total Length
347.5 ft.
Structural Index
3
Structural Quick
5M3M
Structural Rating
690
O&M Index
2
O&M Quick
2M00
O&M Rating
138
Overall Index
3
Overall Quick
Overall Rating
828
Pipe schematic from manhole 08 0340 to 08 0339
MH: 08 0340MH: 08 0339downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 03400 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start3.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.3 ft. MGO - General Observation - 70% MAG COAT214 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 6" - OPEN345 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish345 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish345 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish347.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish347.5 ft. AMH - Downstream Manhole, Survey Ends - 08 0339

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.3 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
0MWL
3.3SAV
345DAGS
0AMH08 0340
2SSS
214TFOPEN
347.5SAV
345SRV
0MWM
345SSS
347.5AMH08 0339
2SRV
2DAGS
3.3MGO70% MAG COAT

Properties (7)

additional_info
SC411832
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2020-09-02T21:34:47-07:00
documentation
PROPIPE
is_lateral_inspection
false