Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 3, 2020, 10:02 AM
  • E 0043_E 0042_08032020_033521.mp4

Date
08/03/2020
W/O
845647
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00028
PipeID
P11270
Time
3:02 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7938
Sewer Name
JOINT OUTFALL E - UNIT 2
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
16
Purpose
Routine Assessment
Project
RFIR_WO_845647_TV01123_AUG2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
E 0042
Downstream MH
E 0043
Dir. of Survey
Upstream
Length Surveyed
474.4 ft.
Total Length
474.4 ft.
Structural Index
4
Structural Quick
5F3R
Structural Rating
465
O&M Index
3
O&M Quick
3100
O&M Rating
3
Overall Index
4
Overall Quick
Overall Rating
468
Pipe schematic from manhole E 0042 to E 0043
MH: E 0042MH: E 0043upstream0 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish0 ft. AMH - Upstream Manhole, Survey Ends - E 00430 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish179.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish179.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start179.1 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start304.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"406.4 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES472.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start474.4 ft. MGO - General Observation - CONNECTION IN MH, 3 O' CLOCK474.4 ft. MWL - Water Level, 5 %of cross sectional area474.4 ft. AMH - Downstream Manhole, Survey Begins - E 0042474.4 ft. MWM - Water Mark, 5 %of cross sectional area

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    295.3 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    295.3 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
295.3SAV
474.4SRV
0MGOCONNECTION IN MH, 3 O' CLOCK
0MWL
295.3SAP
474.4AMHE 0043
0AMHE 0042
169.9TF
68DSZ
2.1SAV
295.3SRV
474.4SAP
0MWM

Properties (7)

additional_info
SC411798
custom_field_three
AGGREGATE PROJECTING/SURFACE REINFORCEMENT VISIBLE
custom_field_two
2
customer
1
datetime
2020-08-03T03:02:09-07:00
documentation
PROPIPE
is_lateral_inspection
false