Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 5, 2020, 05:35 AM
  • E 0038_E 0037_08042020_224128.mp4

Date
08/04/2020
W/O
845647
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00028
PipeID
P11265
Time
10:35 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7939
Sewer Name
JOINT OUTFALL E - UNIT 2
City
COMPTON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
18
Purpose
Routine Assessment
Project
RFIR_WO_845647_TV01123_AUG2020
Sewer Type
Siphon
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
E 0038
Downstream MH
E 0037
Dir. of Survey
Downstream
Length Surveyed
7.1 ft.
Total Length
7.1 ft.
Structural Index
4
Structural Quick
5131
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
8
Pipe schematic from manhole E 0038 to E 0037
MH: E 0038MH: E 0037downstream0 ft. AMH - Upstream Manhole, Survey Begins - E 00380 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area2.1 ft. MGO - General Observation - MAG COATING ATTATCHED3.1 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES3.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start7.1 ft. MSA - Survey Abandoned - VIEW OF D/S SIPHON FROM THE U/S MH7.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (3)

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES

    3.1 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Survey Abandoned - VIEW OF D/S SIPHON FROM THE U/S MH

    7.1 ft. - Survey Abandoned - VIEW OF D/S SIPHON FROM THE U/S MH

Observations (8)

DistanceCodeObservation
0AMHE 0038
7.1MSAVIEW OF D/S SIPHON FROM THE U/S MH
3.1SRV
0MWL
7.1SAP
2.1MGOMAG COATING ATTATCHED
3.1SAP
0MWM

Properties (7)

additional_info
SC411799
custom_field_three
AGGREGATE VISIBLE/ REINFORCEMENT VISIBLE
custom_field_two
2
customer
1
datetime
2020-08-04T22:35:48-07:00
documentation
PROPIPE
is_lateral_inspection
false