Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 5, 2020, 08:38 AM
  • E 0034A_E 0034_08052020_015057.mp4

Date
08/05/2020
W/O
845647
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00028
PipeID
P11261
Time
1:38 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7939
Sewer Name
JOINT OUTFALL E - UNIT 2
City
COMPTON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
18
Purpose
Routine Assessment
Project
RFIR_WO_845647_TV01123_AUG2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
E 0034A
Downstream MH
E 0034
Dir. of Survey
Downstream
Length Surveyed
413.1 ft.
Total Length
413.1 ft.
Structural Index
3
Structural Quick
3B00
Structural Rating
45
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
45
Pipe schematic from manhole E 0034A to E 0034
MH: E 0034AMH: E 0034downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - E 0034A0 ft. MGO - General Observation - CONNECTION IN MH, 9 O' CLOCK2.8 ft. MGO - General Observation - MAG COATING ATTATCHED339.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start413.1 ft. AMH - Downstream Manhole, Survey Ends - E 0034413.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    339.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
0MWL
0MWL
2.8MGOMAG COATING ATTATCHED
0AMHE 0034A
413.1AMHE 0034
339.1SAV
413.1SAV
0MGOCONNECTION IN MH, 9 O' CLOCK

Properties (7)

additional_info
SC411799
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2020-08-05T01:38:40-07:00
documentation
PROPIPE
is_lateral_inspection
false