Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 8, 2020, 09:24 AM
  • 01 1007_01 1006_09082020_023704.mp4

Date
09/08/2020
W/O
844360
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00221
PipeID
P01853
Time
2:24 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8027
Sewer Name
VERNON EXTENSION TRUNK
City
VERNON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
04
Purpose
Routine Assessment
Project
RFIR_WO_844360_TV01271_AUG2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
27 in.
Upstream MH
01 1007
Downstream MH
01 1006
Dir. of Survey
Downstream
Length Surveyed
324.5 ft.
Total Length
324.5 ft.
Structural Index
3
Structural Quick
3L2D
Structural Rating
242
O&M Index
2
O&M Quick
2L00
O&M Rating
130
Overall Index
2
Overall Quick
Overall Rating
372
Pipe schematic from manhole 01 1007 to 01 1006
MH: 01 1007MH: 01 1006downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 10070 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - ROACHES @ MH2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start13.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"16.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"20.5 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start107.7 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN114 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"116.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"145.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish215.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN217.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"274.5 ft. TBC - Tap Break-In Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"281.7 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN316 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"318.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"322 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish322 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish324 ft. MGO - General Observation - ROACHES @ MH324.5 ft. AMH - Downstream Manhole, Survey Ends - 01 1006

Observation photos (4)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    20.5 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    274.5 ft. - Tap Break-In Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

    281.7 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

Observations (23)

DistanceCodeObservation
217.9TFC
281.7TBOPEN
322DAGS
318.9TFC
13.7TFC
274.5TBC
145.1CL
0MWM
324.5AMH01 1006
116.8TFC
0AMH01 1007
2CM
114TFC
0MWL
2DAGS
16.1TFC
107.7TBOPEN
20.5CL
322CM
215.2TFOPEN
316TFC
0MGOROACHES @ MH
324MGOROACHES @ MH

Properties (7)

additional_info
SC411840
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2020-09-08T02:24:57-07:00
documentation
PROPIPE
is_lateral_inspection
false