Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 26, 2016, 11:25 AM
  • 08 0135_08 0134_7262016_043206.mp4

Date
07/26/2016
W/O
0574374
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00006
PipeID
P00191
Time
4:25 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0206
Sewer Name
08 FIGUEROA STREET TRUNK
City
COMPTON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
01
Purpose
Routine Assessment
Project
20160723MDM_FIGUEROA_STREET_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
08 0135
Downstream MH
08 0134
Dir. of Survey
Downstream
Length Surveyed
383.8 ft.
Total Length
383.8 ft.
Structural Index
2
Structural Quick
352C
Structural Rating
51
O&M Index
1
O&M Quick
1400
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
55
Pipe schematic from manhole 08 0135 to 08 0134
MH: 08 0135MH: 08 0134downstream0 ft. MGO - General Observation - HOT OILY FLOW0 ft. AMH - Upstream Manhole, Survey Begins - 4:25AM0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area15.8 ft. FC - Fracture Circumferential, from 11 to 12 o'clock, within 8 inches of joint: YES - SLIGHT15.8 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - HAIRLINE15.8 ft. RFJ - Roots Fine Joint, from 11 to 01 o'clock, within 8 inches of joint: YESR - 3%24.2 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SLIGHT32 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H33.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped42.3 ft. RFJ - Roots Fine Joint, from 10 to 02 o'clock, within 8 inches of joint: YESR - 5%46.9 ft. RFJ - Roots Fine Joint, from 10 to 01 o'clock, within 8 inches of joint: YESR - 2%50.5 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H50.5 ft. RFJ - Roots Fine Joint, from 09 to 12 o'clock, within 8 inches of joint: YESR - 3%59.1 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - H83.2 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - H83.2 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H84.3 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Open94.1 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - H134.5 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - H134.5 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL135.8 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped186.6 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped237.5 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped251.9 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - H251.9 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - H296.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H309.4 ft. MGO - General Observation - 12" VCP316.5 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - SLIGHT316.5 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SLIGHT320.7 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SLIGHT324.7 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL344.9 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - H349.1 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - H356.9 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - H365.1 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - H373.2 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - H383.3 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. OPEN383.8 ft. AMH - Downstream Manhole, Survey Ends - 5:20AM

Observation photos (3)

  • General Observation - 12" VCP

    309.4 ft. - General Observation - 12" VCP

  • Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - SLIGHT

    316.5 ft. - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - SLIGHT

  • Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SLIGHT

    316.5 ft. - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SLIGHT

Observations (39)

DistanceCodeObservation
383.3MGOConn. @ Mh, 3 O' Clock. OPEN
383.8AMH5:20AM
251.9FCH
344.9FCH
84.3TFOpen
32FCH
0MGOHOT OILY FLOW
33.1TFCCapped
135.8TFCCapped
296.4FLH
59.1FLH
83.2FCH
50.5FLH
46.9RFJ2%
134.5FLH
94.1FCH
15.8FCSLIGHT
134.5FCSL
237.5TFCCapped
15.8FCHAIRLINE
365.1FCH
324.7FCSL
320.7FCSLIGHT
50.5RFJ3%
24.2FCSLIGHT
0AMH4:25AM
0MWL
373.2FCH
251.9FCH
309.4MGO12" VCP
316.5FCSLIGHT
0MWM
316.5FCSLIGHT
42.3RFJ5%
83.2FCH
356.9FCH
186.6TFCCapped
349.1FLH
15.8RFJ3%

Properties (6)

custom_field_three
SLIGHT FRACTURES
custom_field_two
3
customer
LACSD
datetime
2016-07-26T04:25:00-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false