Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 21, 2016, 03:29 PM
  • 29 0377_29 0376_7212016_083719.mp4

Date
07/21/2016
W/O
0579968
Weather
Very Dry
Operator/Surveyor
MIRANDA
Sewer ID
Z00537
PipeID
P24414
Time
8:29 AM
Certificate
U-1014-06022542
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7185
Sewer Name
29 21ST STREET SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
03
Purpose
Routine Assessment
Project
20160721AM_21ST_STREET_SEWER
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Upstream MH
29 0377
Downstream MH
29 0376
Dir. of Survey
Downstream
Length Surveyed
333.9 ft.
Total Length
333.9 ft.
Structural Index
2
Structural Quick
4433
Structural Rating
43
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
47
Pipe schematic from manhole 29 0377 to 29 0376
MH: 29 0377MH: 29 0376downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 8:36 AM0 ft. MGO - General Observation - ROACHES INSIDE THE MH.0 ft. MWL - Water Level, 10 %of cross sectional area2.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO, Start2.1 ft. MMC - Material Change, Concrete pipe (non-reinfored)2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start5 ft. MGO - General Observation - CHIPPING41 ft. JSM - Joint Separated Medium41 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES42.1 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN, 50% BLOCKED46.7 ft. JSL - Joint Separated Large59.6 ft. FM - Fracture Multiple, from 10 to 01 o'clock, within 8 inches of joint: YES103.6 ft. MGO - General Observation - CHIPPING108.8 ft. MGO - General Observation - CHIPPING113.9 ft. JSM - Joint Separated Medium127.1 ft. JSL - Joint Separated Large127.1 ft. B - Broken, from 11 to 12 o'clock, within 8 inches of joint: YES143.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN145.2 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES153.7 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"227.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES245.9 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES247.1 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN, 30% BLOCKED254.6 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6" - OPEN277 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES277 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES277 ft. JSM - Joint Separated Medium294.9 ft. JSM - Joint Separated Medium297.5 ft. FM - Fracture Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES323.5 ft. FM - Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES331 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish331 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish331 ft. MGO - General Observation - SEPARATED JOINTS THROUGHOUT THE REACH331 ft. MGO - General Observation - CHIPPING THROUGHOUT THE REACH332 ft. MGO - General Observation - ROACHES INSIDE THE MH.333.9 ft. AMH - Downstream Manhole, Survey Ends - 9:58 AM

Observation photos (19)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

    2.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

  • Material Change, Concrete pipe (non-reinfored)

    2.1 ft. - Material Change, Concrete pipe (non-reinfored)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

  • General Observation - CHIPPING

    5 ft. - General Observation - CHIPPING

  • Joint Separated Medium

    41 ft. - Joint Separated Medium

  • Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    41 ft. - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN, 50% BLOCKED

    42.1 ft. - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN, 50% BLOCKED

  • Joint Separated Large

    46.7 ft. - Joint Separated Large

  • Fracture Multiple, from 10 to 01 o'clock, within 8 inches of joint: YES

    59.6 ft. - Fracture Multiple, from 10 to 01 o'clock, within 8 inches of joint: YES

  • Joint Separated Medium

    113.9 ft. - Joint Separated Medium

  • Joint Separated Large

    127.1 ft. - Joint Separated Large

  • Broken, from 11 to 12 o'clock, within 8 inches of joint: YES

    127.1 ft. - Broken, from 11 to 12 o'clock, within 8 inches of joint: YES

  • Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES

    145.2 ft. - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES

  • Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN, 30% BLOCKED

    247.1 ft. - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN, 30% BLOCKED

  • Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    277 ft. - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES

  • Joint Separated Medium

    277 ft. - Joint Separated Medium

  • Joint Separated Medium

    294.9 ft. - Joint Separated Medium

  • Fracture Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES

    297.5 ft. - Fracture Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

    323.5 ft. - Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

Observations (37)

DistanceCodeObservation
277CL
247.1TFDOPEN, 30% BLOCKED
297.5FM
245.9CL
5MGOCHIPPING
108.8MGOCHIPPING
331SAV
153.7TFA
145.2FC
277FL
323.5FM
331SSS
227.8CL
103.6MGOCHIPPING
127.1JSL
127.1B
2.1SSS
46.7JSL
0MWM
331MGOSEPARATED JOINTS THROUGHOUT THE REACH
41JSM
0AMH8:36 AM
0MGOROACHES INSIDE THE MH.
333.9AMH9:58 AM
294.9JSM
59.6FM
332MGOROACHES INSIDE THE MH.
113.9JSM
2.1MMC
41FL
277JSM
2.1SAV
254.6TFOPEN
0MWL
143.8TFOPEN
42.1TFDOPEN, 50% BLOCKED
331MGOCHIPPING THROUGHOUT THE REACH

Properties (6)

custom_field_three
BROKEN PIPE
custom_field_two
1
customer
LACSD
datetime
2016-07-21T08:29:10-07:00
documentation
MIRANDA, FRANKLIN, SHADLER
is_lateral_inspection
false