Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 16, 2016, 07:37 AM
  • H 0338_H 0337_7162016_012041.mp4

Date
07/16/2016
W/O
0580377
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00175
PipeID
P10788
Time
12:37 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0189
Sewer Name
H JOINT OUTFALL H - UNIT 4
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
19A
Purpose
Capital Improvement Program Assesment
Project
20160716MDM_JOINT_OUTFALL_H_UNIT_4
Material
Reinforced Concrete Pipe
Shape
Circular
Height
63 in.
Upstream MH
H 0338
Downstream MH
H 0337
Dir. of Survey
Downstream
Length Surveyed
8.2 ft.
Total Length
8.2 ft.
Structural Index
4
Structural Quick
5231
Structural Rating
13
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
17
Pipe schematic from manhole H 0338 to H 0337
MH: H 0338MH: H 0337downstream0 ft. MWL - Water Level, 60 %of cross sectional area0 ft. MWM - Water Mark, 70 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 12:45AM1.9 ft. SAP - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG4 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR4 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO, Start - CIRCUM8 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO, Finish8 ft. SAP - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish8.2 ft. MSA - Survey Abandoned - DOWNLEG UPSTREAM SIPHON 1:00AM

Observation photos (5)

  • Water Level, 60 %of cross sectional area

    0 ft. - Water Level, 60 %of cross sectional area

  • Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    1.9 ft. - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    4 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO, Start - CIRCUM

    4 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO, Start - CIRCUM

  • Survey Abandoned - DOWNLEG UPSTREAM SIPHON 1:00AM

    8.2 ft. - Survey Abandoned - DOWNLEG UPSTREAM SIPHON 1:00AM

Observations (9)

DistanceCodeObservation
8SRV
8.2MSADOWNLEG UPSTREAM SIPHON 1:00AM
1.9SAPSEVERE AGG
4SRVCIRCUM REBAR
0MWL
0MWM
0AMH12:45AM
8SAP
4SRVCIRCUM

Properties (7)

additional_info
DOWNLEG UPSTREAM SIPHON
custom_field_three
VISIBLE CIRCUM REBAR
custom_field_two
2
customer
LACSD
datetime
2016-07-16T00:37:31-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false