Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 12, 2016, 09:17 AM
  • G 0113_G 0086_7122016_022244.mp4

Date
07/12/2016
W/O
0580129
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z01180
PipeID
P02174
Time
2:17 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
HO182
Sewer Name
G JOINT OUTFALL G - UNIT 8
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
16
Purpose
Capital Improvement Program Assesment
Project
20160709MDM_JOINT_OUTFALL_G_UNIT_8
Material
RCP-CTL
Shape
Circular
Height
48 in.
Upstream MH
G 0113
Downstream MH
G 0086
Dir. of Survey
Downstream
Length Surveyed
322.7 ft.
Total Length
322.7 ft.
Structural Index
5
Structural Quick
5841
Structural Rating
44
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
5
Overall Quick
Overall Rating
48
Pipe schematic from manhole G 0113 to G 0086
MH: G 0113MH: G 0086downstream0 ft. MWM - Water Mark, 55 %of cross sectional area0 ft. MWL - Water Level, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 2:00AM0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active2 ft. MGO - General Observation - MISSING TILES 100% START 9:00 TO 3:002 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR CORRODED & MISSING2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG11.7 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - BROKEN MISSING REBAR26.4 ft. MGO - General Observation - 2 ROWS TILES IN PLACE74 ft. SRC - Surface Reinforcement Corroded, from 09 to 12 o'clock, within 8 inches of joint: NO - BROKEN REBAR80.2 ft. MGO - General Observation - TILES IN PLACE 80%97.9 ft. MGO - General Observation - TILES IN PLACE 70% START126.8 ft. MGO - General Observation - TILES IN PLACE 70% FINISH176.7 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES197.9 ft. MGO - General Observation - MISSING TILES 20% START212.9 ft. MGO - General Observation - MISSING TILES 20% FINISH238 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES243.7 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - BROKEN REBAR248.7 ft. SRC - Surface Reinforcement Corroded, from 12 to 03 o'clock, within 8 inches of joint: NO - BROKEN REBAR280.8 ft. MGO - General Observation - 2 ROWS TLIES IN PLACE298.4 ft. MGO - General Observation - 2 ROWS TILES IN PLACE302 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN MISSING REBAR LONG & CIRCUM322.3 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active LARGE INCOMING322.3 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - BROKEN MISSING LONG & CIRCUM REBAR322.3 ft. MGO - General Observation - MISSING TILES 100% FINISH322.3 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG322.7 ft. AMH - Downstream Manhole, Survey Ends - 2:35AM

Observation photos (14)

  • General Observation - MISSING TILES 100% START 9:00 TO 3:00

    2 ft. - General Observation - MISSING TILES 100% START 9:00 TO 3:00

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR CORRODED & MISSING

    2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR CORRODED & MISSING

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - BROKEN MISSING REBAR

    11.7 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - BROKEN MISSING REBAR

  • General Observation - 2 ROWS TILES IN PLACE

    26.4 ft. - General Observation - 2 ROWS TILES IN PLACE

  • Surface Reinforcement Corroded, from 09 to 12 o'clock, within 8 inches of joint: NO - BROKEN REBAR

    74 ft. - Surface Reinforcement Corroded, from 09 to 12 o'clock, within 8 inches of joint: NO - BROKEN REBAR

  • General Observation - TILES IN PLACE 80%

    80.2 ft. - General Observation - TILES IN PLACE 80%

  • General Observation - TILES IN PLACE 70% START

    97.9 ft. - General Observation - TILES IN PLACE 70% START

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES

    176.7 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES

  • General Observation - MISSING TILES 20% START

    197.9 ft. - General Observation - MISSING TILES 20% START

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES

    238 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - BROKEN REBAR

    243.7 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - BROKEN REBAR

  • Surface Reinforcement Corroded, from 12 to 03 o'clock, within 8 inches of joint: NO - BROKEN REBAR

    248.7 ft. - Surface Reinforcement Corroded, from 12 to 03 o'clock, within 8 inches of joint: NO - BROKEN REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN MISSING REBAR LONG & CIRCUM

    302 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN MISSING REBAR LONG & CIRCUM

Observations (28)

DistanceCodeObservation
0MWM
80.2MGOTILES IN PLACE 80%
126.8MGOTILES IN PLACE 70% FINISH
243.7SRCBROKEN REBAR
2MGOMISSING TILES 100% START 9:00 TO 3:00
74SRCBROKEN REBAR
212.9MGOMISSING TILES 20% FINISH
322.7AMH2:35AM
322.3MGOConn. @ Mh, 3 O' Clock. Active LARGE INCOMING
197.9MGOMISSING TILES 20% START
2SRCLONG & CIRCUM REBAR CORRODED & MISSING
11.7SRCBROKEN MISSING REBAR
322.3SRCBROKEN MISSING LONG & CIRCUM REBAR
298.4MGO2 ROWS TILES IN PLACE
238SRC
26.4MGO2 ROWS TILES IN PLACE
248.7SRCBROKEN REBAR
322.3MGOMISSING TILES 100% FINISH
322.3SAMSEVERE AGG
0MWL
97.9MGOTILES IN PLACE 70% START
176.7SRV
0AMH2:00AM
0MGOConn. @ Mh, 9 O' Clock. Active
302SRCBROKEN MISSING REBAR LONG & CIRCUM
0MGOConn. @ Mh, 3 O' Clock. Active
2SAMSEVERE AGG
280.8MGO2 ROWS TLIES IN PLACE

Properties (6)

custom_field_three
CORRODED MISSING REBAR
custom_field_two
2
customer
LACSD
datetime
2016-07-12T02:17:51-07:00
documentation
MARTIN,MANANES,OLIVER 111
is_lateral_inspection
false