Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 2, 2016, 12:38 PM
  • 29 0386_29 0385_722016_054252.mp4

Date
07/02/2016
W/O
0579968
Weather
Dry
Operator/Surveyor
MIRANDA
Sewer ID
Z00537
PipeID
P24423
Time
5:38 AM
Certificate
U-1014-06022542
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7168
Sewer Name
29 21ST STREET SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
03
Purpose
Routine Assessment
Project
20160702AM_21ST_STREET_SEWER
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Upstream MH
29 0385
Downstream MH
29 0386
Dir. of Survey
Upstream
Length Surveyed
303.3 ft.
Total Length
303.3 ft.
Structural Index
3
Structural Quick
413A
Structural Rating
41
O&M Index
2
O&M Quick
3124
O&M Rating
15
Overall Index
2
Overall Quick
Overall Rating
56
Pipe schematic from manhole 29 0385 to 29 0386
MH: 29 0385MH: 29 0386upstream0 ft. AMH - Upstream Manhole, Survey Ends - 6:33 AM1.5 ft. MGO - General Observation - ROACHES INSIDE THE MH.1.9 ft. MGO - General Observation - SLIGHT GREASE THROUGHOUT THE REACH3 ft. RTJ - Roots Tap Joint, from 02 to 07 o'clock, 10 %, within 8 inches of joint: YESR3 ft. MGO - General Observation - CHIPPING AROUND THE JOINT3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish3 ft. FC - Fracture Circumferential, from 01 to 02 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN4.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"5.6 ft. RMJ - Roots Medium Joint, from 07 to 05 o'clock, 15 %, within 8 inches of joint: YESR - TAP ROOTS ALSO11.4 ft. RTJ - Roots Tap Joint, from 08 to 09 o'clock, 5 %, within 8 inches of joint: YESR30 ft. RFJ - Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YESR33.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES49.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"50.8 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES55.4 ft. TBA - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: YES, 4", 6"66.1 ft. RTJ - Roots Tap Joint, at 08 o'clock, 5 %, within 8 inches of joint: YESR69 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN97.8 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE, BROKEN97.8 ft. RFL - Roots Fine Lateral, from 02 to 04 o'clock99.1 ft. RFJ - Roots Fine Joint, from 02 to 05 o'clock, within 8 inches of joint: YESR99.1 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES100.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"107.8 ft. RFJ - Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YESR120 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES135.1 ft. MGO - General Observation - CHIPPING151.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"189.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN197 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"199.5 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: YES, 6"225.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start234.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES247.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"249 ft. CM - Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES255 ft. CM - Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES258.2 ft. FM - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES265.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"269.9 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES275.9 ft. CM - Crack Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES303.3 ft. MWL - Water Level, 5 %of cross sectional area303.3 ft. MGO - General Observation - ROACHES INSIDE THE MH.303.3 ft. MWM - Water Mark, 10 %of cross sectional area303.3 ft. AMH - Downstream Manhole, Survey Begins - 5:42 AM

Observation photos (19)

  • Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

    45.1 ft. - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

    54.3 ft. - Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    78.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN

    113.8 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN

  • General Observation - CHIPPING

    168.2 ft. - General Observation - CHIPPING

  • Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    183.3 ft. - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YESR

    195.5 ft. - Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YESR

  • Roots Fine Joint, from 02 to 05 o'clock, within 8 inches of joint: YESR

    204.2 ft. - Roots Fine Joint, from 02 to 05 o'clock, within 8 inches of joint: YESR

  • Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    204.2 ft. - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE, BROKEN

    205.5 ft. - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE, BROKEN

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN

    234.3 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN

  • Roots Tap Joint, at 08 o'clock, 5 %, within 8 inches of joint: YESR

    237.2 ft. - Roots Tap Joint, at 08 o'clock, 5 %, within 8 inches of joint: YESR

  • Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    252.5 ft. - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    270 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Roots Tap Joint, from 08 to 09 o'clock, 5 %, within 8 inches of joint: YESR

    291.9 ft. - Roots Tap Joint, from 08 to 09 o'clock, 5 %, within 8 inches of joint: YESR

  • Roots Medium Joint, from 07 to 05 o'clock, 15 %, within 8 inches of joint: YESR - TAP ROOTS ALSO

    297.7 ft. - Roots Medium Joint, from 07 to 05 o'clock, 15 %, within 8 inches of joint: YESR - TAP ROOTS ALSO

  • Roots Tap Joint, from 02 to 07 o'clock, 10 %, within 8 inches of joint: YESR

    300.3 ft. - Roots Tap Joint, from 02 to 07 o'clock, 10 %, within 8 inches of joint: YESR

  • General Observation - CHIPPING AROUND THE JOINT

    300.3 ft. - General Observation - CHIPPING AROUND THE JOINT

  • Fracture Circumferential, from 01 to 02 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN

    300.3 ft. - Fracture Circumferential, from 01 to 02 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN

Observations (42)

DistanceCodeObservation
301.4MGOSLIGHT GREASE THROUGHOUT THE REACH
103.8TFC
0MWL
303.3AMH6:33 AM
0MGOROACHES INSIDE THE MH.
106.3TFA
270FL
204.2RFJ
300.3RTJ
27.4CM
252.5FL
38TFC
291.9RTJ
301.8MGOROACHES INSIDE THE MH.
69CM
195.5RFJ
299.1TFA
300.3MGOCHIPPING AROUND THE JOINT
151.6TFC
203TFC
237.2RTJ
253.9TFC
205.5TFDACTIVE, BROKEN
247.9TBA
273.3RFJ
113.8FLPOSSIBLY BROKEN
205.5RFL
183.3FL
78.1CM
300.3CM
168.2MGOCHIPPING
204.2FL
54.3CM
45.1FM
0MWM
0AMH5:42 AM
297.7RMJTAP ROOTS ALSO
55.5TFA
33.4CL
234.3FLPOSSIBLY BROKEN
300.3FCPOSSIBLY BROKEN
48.3CM

Properties (6)

custom_field_three
POSSIBLE BROKEN PIPE
custom_field_two
1
customer
LACSD
datetime
2016-07-02T05:38:32-07:00
documentation
MIRANDA & SHADLER
is_lateral_inspection
false