Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 10, 2020, 10:21 AM
  • 02 0412_02 0411 _08102020_033554.mp4

Date
08/10/2020
W/O
844559
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00256
PipeID
P02734
Time
3:21 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7900
Sewer Name
DOWNEY-BELLFLOWER RELIEF TRUNK, SECTION 4
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
32
Purpose
Routine Assessment
Project
WO_844559_TV02193_AUG2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
21 in.
Upstream MH
02 0412
Downstream MH
02 0411
Dir. of Survey
Downstream
Length Surveyed
337.3 ft.
Total Length
337.3 ft.
Structural Index
3
Structural Quick
3L2L
Structural Rating
335
O&M Index
2
O&M Quick
2M00
O&M Rating
136
Overall Index
2
Overall Quick
Overall Rating
471
Pipe schematic from manhole 02 0412 to 02 0411
MH: 02 0412MH: 02 0411downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/OPEN0 ft. AMH - Upstream Manhole, Survey Begins - 02 04120 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start26.5 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6"51.8 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN87.5 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN97.7 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN143.3 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN204.4 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN250.5 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN296.2 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6"311.5 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6"335 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish335 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish335.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish337.3 ft. AMH - Downstream Manhole, Survey Ends - 02 0411

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (20)

DistanceCodeObservation
0MWL
335SSS
97.7TBOPEN
335DAGS
337.3AMH02 0411
311.5TBA
0MGOCONN @ MH 3 O'CLOCK/OPEN
143.3TBOPEN
335.2CM
26.5TBC
2DAGS
2SSS
250.5TBOPEN
51.8TBOPEN
296.2TBA
0AMH02 0412
87.5TBOPEN
204.4TBOPEN
0MWM
2CM

Properties (7)

additional_info
SC411740
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2020-08-10T03:21:24-07:00
documentation
PRO PIPE
is_lateral_inspection
false