Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 10, 2020, 09:27 AM
  • 02 2378_02 0408 _08102020_024059.mp4

Date
08/10/2020
W/O
844559
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00256
PipeID
P02730
Time
2:27 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7900
Sewer Name
DOWNEY-BELLFLOWER RELIEF TRUNK, SECTION 4
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
32
Purpose
Routine Assessment
Project
WO_844559_TV02193_AUG2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
21 in.
Upstream MH
02 2378
Downstream MH
02 0408
Dir. of Survey
Downstream
Length Surveyed
230.9 ft.
Total Length
230.9 ft.
Structural Index
3
Structural Quick
3P00
Structural Rating
249
O&M Index
2
O&M Quick
2H11
O&M Rating
91
Overall Index
3
Overall Quick
Overall Rating
340
Pipe schematic from manhole 02 2378 to 02 0408
MH: 02 2378MH: 02 0408downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 23780 ft. MGO - General Observation - ROACHES @ MH0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start8.5 ft. RFC - Roots Fine Connection, at 12 o'clock, within 8 inches of joint: YES8.5 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"9.8 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"25.9 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN27.8 ft. CM - Crack Multiple, from 10 to 12 o'clock, within 8 inches of joint: YES30 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN43.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start81.3 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN101.8 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN132.4 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN228 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish229.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish229.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish230.9 ft. MGO - General Observation - STOP LOG CONN @ MH 12 O'CLOCK/UNKNOWN230.9 ft. AMH - Downstream Manhole, Survey Ends - 02 0408230.9 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE

Observation photos (5)

  • General Observation - ROACHES @ MH

    0 ft. - General Observation - ROACHES @ MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Roots Fine Connection, at 12 o'clock, within 8 inches of joint: YES

    8.5 ft. - Roots Fine Connection, at 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 10 to 12 o'clock, within 8 inches of joint: YES

    27.8 ft. - Crack Multiple, from 10 to 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    43.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (22)

DistanceCodeObservation
25.9TBOPEN
228CM
43.3CM
30TBOPEN
230.9MGOSTOP LOG CONN @ MH 12 O'CLOCK/UNKNOWN
81.3TBOPEN
9.8TBA
101.8TBOPEN
0MWL
229.4DAGS
8.5RFC
229.4CM
2CM
0AMH02 2378
8.5TBA
132.4TBOPEN
27.8CM
2DAGS
0MGOROACHES @ MH
230.9AMH02 0408
230.9MGOCONN @ MH 9 O'CLOCK/ACTIVE
0MWM

Properties (6)

custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2020-08-10T02:27:34-07:00
documentation
PRO PIPE
is_lateral_inspection
false