Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 3, 2020, 04:51 AM
  • 19 0067_C 0373_09022020_221023.mp4

Date
09/02/2020
W/O
844369
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00724
PipeID
P15099
Time
9:51 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7977
Sewer Name
ELAINE AVENUE TRUNK
City
HAWAIIAN GARDENS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
06
Purpose
Routine Assessment
Project
RFIR_WO_844369_TV19073_AUG2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
19 0067
Downstream MH
C 0373
Dir. of Survey
Downstream
Length Surveyed
311.2 ft.
Total Length
311.2 ft.
Structural Index
2
Structural Quick
3F2K
Structural Rating
226
O&M Index
2
O&M Quick
2L00
O&M Rating
128
Overall Index
2
Overall Quick
Overall Rating
354
Pipe schematic from manhole 19 0067 to C 0373
MH: 19 0067MH: C 0373downstream0 ft. MGO - General Observation - CONN @ MH 3 O' CLOCK/0 ft. MGO - General Observation - ROACHES @ MH0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 19 00672 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: NO, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start25 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"28.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"35 ft. MWL - Water Level, 20 %of cross sectional area74.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"77.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"82.2 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES82.2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 02 to 04 o'clock, , within 8 inches of joint: YES123.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"126.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"143.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start172.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"175 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"224.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"227.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"268 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"270.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"277.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"306.8 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES309 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish310.3 ft. MGO - General Observation - ROACHES @ MH310.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: NO, Finish310.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish311.2 ft. AMH - Downstream Manhole, Survey Ends - C 0373

Observation photos (8)

  • General Observation - ROACHES @ MH

    0 ft. - General Observation - ROACHES @ MH

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: NO, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: NO, Start

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    82.2 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 02 to 04 o'clock,  , within 8 inches of joint: YES

    82.2 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 02 to 04 o'clock, , within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    143.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES

    306.8 ft. - Deposits Attached Encrustation, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES

  • General Observation - ROACHES @ MH

    310.3 ft. - General Observation - ROACHES @ MH

Observations (31)

DistanceCodeObservation
175TFC
310.3MGOROACHES @ MH
311.2AMHC 0373
268TFC
77.2TFC
2CM
28.3TFC
2DAGS
172.3TFC
123.3TFA
82.2CL
35MWL
2SSS
306.8DAE
0MGOCONN @ MH 3 O' CLOCK/
310.3DAGS
310.3CM
0MGOROACHES @ MH
82.2DAE
0MWL
143.4CM
25TFC
227.9TFC
74.1TFC
224.5TFC
277.8TFA
126.5TFC
309SSS
270.9TFC
0MWM
0AMH19 0067

Properties (7)

additional_info
SC411868
custom_field_three
MULTIPLE CRACKS/ENCRUSTATION
custom_field_two
3
customer
1
datetime
2020-09-02T21:51:29-07:00
documentation
PRO PIPE
is_lateral_inspection
false