Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 2, 2020, 09:14 AM
  • 08 0346_08 DAVIDS_09022020_022320.mp4

Date
09/02/2020
W/O
844355
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00003
PipeID
P23452
Time
2:14 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8017
Sewer Name
DAVIDSON CITY TRUNK, SECTS 1,2,&3
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
15
Purpose
Routine Assessment
Project
WO_844355_TV08001_AUG2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
08 0346
Downstream MH
08 DAVIDS
Dir. of Survey
Downstream
Length Surveyed
320.5 ft.
Total Length
320.5 ft.
Structural Index
3
Structural Quick
3L2L
Structural Rating
315
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
315
Pipe schematic from manhole 08 0346 to 08 DAVIDS
MH: 08 0346MH: 08 DAVIDSdownstream0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 03462.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start318.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish318.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish320 ft. MGO - General Observation - LONGITUDINAL FRACTURE @ 10 O'CLOCK OF VCP CAP320 ft. MGO - General Observation - VCP CAP PRESENT @ "O8 DAVIDS"320.5 ft. AMH - Downstream Manhole, Survey Ends - 08 DAVIDS

Observation photos (2)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK
0MWL
320MGOLONGITUDINAL FRACTURE @ 10 O'CLOCK OF VCP CAP
318.9SAP
2.1SSS
0MWM
320.5AMH08 DAVIDS
320MGOVCP CAP PRESENT @ "O8 DAVIDS"
2.1SAP
318.9SSS
0AMH08 0346

Properties (7)

additional_info
SC411830
custom_field_three
FRACTURE - AGGREGATE PROJECTING
custom_field_two
2
customer
1
datetime
2020-09-02T02:14:54-07:00
documentation
PROPIPE
is_lateral_inspection
false