- Date
- 08/26/2020
- W/O
- 844349
- Weather
- Dry
- Operator/Surveyor
- JOSE GONZALEZ
- Sewer ID
- Z00648
- PipeID
- P13197
- Time
- 10:26 PM
- Certificate
- U-0720-70309215
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K7968
- Sewer Name
- ARROYO SECO TRUNK, SECTION 5
- City
- S. PASADENA
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 16
- Page No.
- 17
- Purpose
- Routine Assessment
- Project
- RFIR_WO_844349_TV16081_AUG2020
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 18 in.
- Width
- 18 in.
- Upstream MH
- 16 0165
- Downstream MH
- 16 0164
- Dir. of Survey
- Downstream
- Length Surveyed
- 504.7 ft.
- Total Length
- 504.7 ft.
- Structural Index
- 3
- Structural Quick
- 4F3S
- Structural Rating
- 636
- O&M Index
- 2
- O&M Quick
- 2S11
- O&M Rating
- 201
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 837
Pipe schematic from manhole 16 0165 to 16 0164 Observation photos (4)

2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

132.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

396 ft. - Roots Fine Connection, at 09 o'clock, within 8 inches of joint: YES