Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 2, 2020, 05:43 AM
  • 08 0485_08 0484 _09012020_234028.mp4

Date
09/01/2020
W/O
844345
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00019
PipeID
P00543
Time
10:43 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8015
Sewer Name
SEPULVEDA-FIGUEROA STREET CONNECTING TRUNK
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_844345_TV08165_AUG2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
36 in.
Upstream MH
08 0484
Downstream MH
08 0485
Dir. of Survey
Upstream
Length Surveyed
220 ft.
Total Length
220 ft.
Structural Index
4
Structural Quick
4H00
Structural Rating
172
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
172
Pipe schematic from manhole 08 0484 to 08 0485
MH: 08 0484MH: 08 0485upstream0 ft. AMH - Upstream Manhole, Survey Ends - 08 04851.8 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish1.8 ft. RPP - Repair Patch, from 12 to 12 o'clock, within 8 inches of joint: YES120 ft. MGO - General Observation - ALIGNMENT LEFT 10% TO U/S MH161.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"214.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"217.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start220 ft. MWM - Water Mark, 5 %of cross sectional area220 ft. AMH - Downstream Manhole, Survey Begins - 08 0484220 ft. MWL - Water Level, 5 %of cross sectional area

Observation photos (2)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Repair Patch, from 12 to 12 o'clock, within 8 inches of joint: YES

    218.2 ft. - Repair Patch, from 12 to 12 o'clock, within 8 inches of joint: YES

Observations (10)

DistanceCodeObservation
2.1FM
0MWM
0AMH08 0484
58.7TFC
100MGOALIGNMENT LEFT 10% TO U/S MH
218.2FM
220AMH08 0485
0MWL
5.6TFC
218.2RPP

Properties (7)

additional_info
SC411828
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2020-09-01T22:43:40-07:00
documentation
PROPIPE
is_lateral_inspection
false