Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 2, 2020, 09:32 AM
  • 32 1133_32 1132 _07022020_024231.mp4

Date
07/02/2020
W/O
838955
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00842
PipeID
P19584
Time
2:32 AM
Certificate
U-111-11880
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7865
Sewer Name
SOLEDAD CANYON TRUNK, SECTION 5
City
SANTA CLARITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
11
Purpose
Routine Assessment
Project
WO_838955_TV32057_JUL2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
32 1132
Downstream MH
32 1133
Dir. of Survey
Upstream
Length Surveyed
222.3 ft.
Total Length
222.3 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
3121
O&M Rating
5
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 32 1132 to 32 1133
MH: 32 1132MH: 32 1133upstream0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish0 ft. OBZ - Obstacles Other, 20 %of cross sectional area, from 05 to 09 o'clock - UNKNOWN0 ft. MSA - Survey Abandoned - DUE TO OBSTRUCTION, REVERSAL COMPLETE.165 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"168.5 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"220.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start222.3 ft. AMH - Downstream Manhole, Survey Begins - 32 1132222.3 ft. MWM - Water Mark, 25 %of cross sectional area222.3 ft. MWL - Water Level, 20 %of cross sectional area

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Obstacles Other, 20 %of cross sectional area, from 05 to 09 o'clock - UNKNOWN

    222.3 ft. - Obstacles Other, 20 %of cross sectional area, from 05 to 09 o'clock - UNKNOWN

  • Survey Abandoned - DUE TO OBSTRUCTION, REVERSAL COMPLETE.

    222.3 ft. - Survey Abandoned - DUE TO OBSTRUCTION, REVERSAL COMPLETE.

Observations (9)

DistanceCodeObservation
0AMH32 1132
222.3DAGS
2DAGS
53.8TBA
0MWM
57.3TBA
222.3OBZUNKNOWN
222.3MSADUE TO OBSTRUCTION, REVERSAL COMPLETE.
0MWL

Properties (7)

additional_info
SC411704
custom_field_three
ABANDONED DUE TO OBSTRUCTION, COMPLETED REVESAL
custom_field_two
3
customer
1
datetime
2020-07-02T02:32:42-07:00
documentation
PRO PIPE
is_lateral_inspection
false