Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 2, 2020, 08:45 AM
  • 32 1133_32 1132 _07022020_015537.mp4

Date
07/02/2020
W/O
838955
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00842
PipeID
P19584
Time
1:45 AM
Certificate
U-111-11880
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7865
Sewer Name
SOLEDAD CANYON TRUNK, SECTION 5
City
SANTA CLARITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
11
Purpose
Routine Assessment
Project
WO_838955_TV32057_JUL2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
32 1133
Downstream MH
32 1132
Dir. of Survey
Downstream
Length Surveyed
121.2 ft.
Total Length
121.2 ft.
Structural Index
3
Structural Quick
413D
Structural Rating
73
O&M Index
2
O&M Quick
4131
O&M Rating
55
Overall Index
3
Overall Quick
Overall Rating
128
Pipe schematic from manhole 32 1133 to 32 1132
MH: 32 1133MH: 32 1132downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 32 11330 ft. MGO - General Observation - CAPPED ("PLATE") CONNECTION @ 3 O'CLOCK - U/S MH2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start7.9 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start13.7 ft. FM - Fracture Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES24 ft. MGO - General Observation - POSSIBLE JOINT SEAL HANGING APPROXIMATELY .3' @ 12 O'CLOCK41.3 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"121.2 ft. OBZ - Obstacles Other, 15 %of cross sectional area, from 04 to 08 o'clock - UNKNOWN121.2 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish121.2 ft. MSA - Survey Abandoned - DUE TO UNKNOWN OBSTRUCTION121.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    7.9 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

    13.7 ft. - Fracture Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

  • Obstacles Other, 15 %of cross sectional area, from 04 to 08 o'clock - UNKNOWN

    121.2 ft. - Obstacles Other, 15 %of cross sectional area, from 04 to 08 o'clock - UNKNOWN

  • Survey Abandoned - DUE TO UNKNOWN OBSTRUCTION

    121.2 ft. - Survey Abandoned - DUE TO UNKNOWN OBSTRUCTION

Observations (13)

DistanceCodeObservation
121.2OBZUNKNOWN
41.3TFA
121.2CM
7.9CM
13.7FM
0MWM
0MWL
121.2MSADUE TO UNKNOWN OBSTRUCTION
24MGOPOSSIBLE JOINT SEAL HANGING APPROXIMATELY .3' @ 12 O'CLOCK
0AMH32 1133
2DAGS
121.2DAGS
0MGOCAPPED ("PLATE") CONNECTION @ 3 O'CLOCK - U/S MH

Properties (7)

additional_info
SC411704
custom_field_three
ABANDONED DUE TO OBSTRUCTION
custom_field_two
5
customer
1
datetime
2020-07-02T01:45:38-07:00
documentation
PRO PIPE
is_lateral_inspection
false