Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 12, 2020, 07:55 AM
  • C 0094_C 0093_9122020_005508.mp4

Date
09/12/2020
W/O
0834128
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00122
PipeID
P09561
Time
12:55 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1563
Sewer Name
C JOINT OUTFALL C - UNIT 3C
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
23
Purpose
Capital Improvement Program Assesment
Project
20200910_JOINT_OUTFALL_C_UNIT_3C
Material
Reinforced Concrete Pipe
Shape
Circular
Height
57 in.
Upstream MH
C 0094
Downstream MH
C 0093
Dir. of Survey
Downstream
Length Surveyed
770.2 ft.
Total Length
770.2 ft.
Structural Index
4
Structural Quick
4621
Structural Rating
26
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
26
Pipe schematic from manhole C 0094 to C 0093
MH: C 0094MH: C 0093downstream0 ft. AMH - Upstream Manhole, Survey Begins - 1:10AM0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 30 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE2 ft. MGO - General Observation - MAG COAT 95% START2 ft. MGO - General Observation - CONCRETE BEAM AT 12:00 MISSING SEVERE AGG AND FALLING APART2 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG UNDER MAG COAT21.8 ft. SAM - Surface Aggregate Missing, at 12 o'clock, within 8 inches of joint: NO - CONCRETE BEAM FALLING APART44.5 ft. SAM - Surface Aggregate Missing, from 12 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG182.9 ft. SAM - Surface Aggregate Missing, from 10 to 12 o'clock, within 8 inches of joint: NO - SEVERE AGG187.5 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG379.4 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG770.2 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG770.2 ft. MGO - General Observation - MAG COAT 95% FINISH770.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE770.2 ft. MGO - General Observation - CONCRETE BEAM AT 12:00 FALLING APART770.2 ft. MGO - General Observation - DEBREIE ON CABLE

Observation photos (10)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • General Observation - MAG COAT 95% START

    2 ft. - General Observation - MAG COAT 95% START

  • General Observation - CONCRETE BEAM AT 12:00 MISSING SEVERE AGG AND FALLING APART

    2 ft. - General Observation - CONCRETE BEAM AT 12:00 MISSING SEVERE AGG AND FALLING APART

  • Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG UNDER MAG COAT

    2 ft. - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG UNDER MAG COAT

  • Surface Aggregate Missing, at 12 o'clock, within 8 inches of joint: NO - CONCRETE BEAM FALLING APART

    21.8 ft. - Surface Aggregate Missing, at 12 o'clock, within 8 inches of joint: NO - CONCRETE BEAM FALLING APART

  • Surface Aggregate Missing, from 12 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

    44.5 ft. - Surface Aggregate Missing, from 12 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Aggregate Missing, from 10 to 12 o'clock, within 8 inches of joint: NO - SEVERE AGG

    182.9 ft. - Surface Aggregate Missing, from 10 to 12 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

    187.5 ft. - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

    379.4 ft. - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • General Observation - DEBREIE ON CABLE

    770.2 ft. - General Observation - DEBREIE ON CABLE

Observations (17)

DistanceCodeObservation
2SSSBLISTERING PEELING CONCRETE
770.2SAMSEVERE AGG
0AMH1:10AM
44.5SAMSEVERE AGG
187.5SAMSEVERE AGG
770.2MGOMAG COAT 95% FINISH
2MGOMAG COAT 95% START
0MWM
770.2SSSBLISTERING PEELING CONCRETE
770.2MGOCONCRETE BEAM AT 12:00 FALLING APART
182.9SAMSEVERE AGG
0MWL
2MGOCONCRETE BEAM AT 12:00 MISSING SEVERE AGG AND FALLING APART
2SAMSEVERE AGG UNDER MAG COAT
770.2MGODEBREIE ON CABLE
379.4SAMSEVERE AGG
21.8SAMCONCRETE BEAM FALLING APART

Properties (6)

custom_field_three
SEVERE AGG MISSING
custom_field_two
2
customer
LACSD
datetime
2020-09-12T00:55:03-07:00
documentation
MARTIN,OLIVER 111-BARR,CASTILLO
is_lateral_inspection
false