Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 11, 2020, 08:17 AM
  • C 0095_C 0094_9112020_011852.mp4

Date
09/11/2020
W/O
0834128
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00122
PipeID
P09562
Time
1:17 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1561
Sewer Name
C JOINT OUTFALL C - UNIT 3C
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
23
Purpose
Capital Improvement Program Assesment
Project
20200910_JOINT_OUTFALL_C_UNIT_3C
Material
Reinforced Concrete Pipe
Shape
Circular
Height
57 in.
Upstream MH
C 0095
Downstream MH
C 0094
Dir. of Survey
Downstream
Length Surveyed
1049.7 ft.
Total Length
1049.7 ft.
Structural Index
4
Structural Quick
4921
Structural Rating
38
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
42
Pipe schematic from manhole C 0095 to C 0094
MH: C 0095MH: C 0094downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:45AM2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE2 ft. MGO - General Observation - CONCRETE BEAM AT 12:00 MISSING SEVERE AGG AND FALLING APART START2 ft. MGO - General Observation - MAG COAT 85% START2 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG4 ft. IW - Infiltration Weeper, from 11 to 01 o'clock, within 8 inches of joint: NO15.8 ft. SAM - Surface Aggregate Missing, from 12 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG39.7 ft. SAM - Surface Aggregate Missing, from 12 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG110.3 ft. SAM - Surface Aggregate Missing, at 12 o'clock, within 8 inches of joint: NO - CONCRETE BEAM FALLING APART165.7 ft. SAM - Surface Aggregate Missing, from 12 to 02 o'clock, within 8 inches of joint: YES - SEVERE AGG207.2 ft. SAM - Surface Aggregate Missing, from 10 to 12 o'clock, within 8 inches of joint: YES - SEVERE AGG277.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start412.5 ft. SAM - Surface Aggregate Missing, from 12 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG599.3 ft. SAM - Surface Aggregate Missing, from 10 to 12 o'clock, within 8 inches of joint: NO - SEVERE AGG882.3 ft. SAM - Surface Aggregate Missing, from 10 to 12 o'clock, within 8 inches of joint: NO - SEVERE AGG1010.1 ft. MGP - General Photograph - RAG TYPE DEBRIE WRAPPED ON CCTV CABLE1010.2 ft. MGO - General Observation - DEBRIE ON CABLE1049 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG1049 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE1049 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish1049.7 ft. AMH - Downstream Manhole, Survey Ends - 3:05AM

Observation photos (14)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • General Observation - CONCRETE BEAM AT 12:00 MISSING SEVERE AGG AND FALLING APART START

    2 ft. - General Observation - CONCRETE BEAM AT 12:00 MISSING SEVERE AGG AND FALLING APART START

  • General Observation - MAG COAT 85% START

    2 ft. - General Observation - MAG COAT 85% START

  • Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Aggregate Missing, from 12 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

    15.8 ft. - Surface Aggregate Missing, from 12 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Aggregate Missing, from 12 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

    39.7 ft. - Surface Aggregate Missing, from 12 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Aggregate Missing, at 12 o'clock, within 8 inches of joint: NO - CONCRETE BEAM FALLING APART

    110.3 ft. - Surface Aggregate Missing, at 12 o'clock, within 8 inches of joint: NO - CONCRETE BEAM FALLING APART

  • Surface Aggregate Missing, from 10 to 12 o'clock, within 8 inches of joint: YES - SEVERE AGG

    207.2 ft. - Surface Aggregate Missing, from 10 to 12 o'clock, within 8 inches of joint: YES - SEVERE AGG

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    277.7 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Missing, from 12 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

    412.5 ft. - Surface Aggregate Missing, from 12 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Aggregate Missing, from 10 to 12 o'clock, within 8 inches of joint: NO - SEVERE AGG

    599.3 ft. - Surface Aggregate Missing, from 10 to 12 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Aggregate Missing, from 10 to 12 o'clock, within 8 inches of joint: NO - SEVERE AGG

    882.3 ft. - Surface Aggregate Missing, from 10 to 12 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • General Photograph - RAG TYPE DEBRIE WRAPPED ON CCTV CABLE

    1010.1 ft. - General Photograph - RAG TYPE DEBRIE WRAPPED ON CCTV CABLE

  • General Observation - DEBRIE ON CABLE

    1010.2 ft. - General Observation - DEBRIE ON CABLE

Observations (23)

DistanceCodeObservation
277.7DAGS
0MWM
207.2SAMSEVERE AGG
0MWL
1010.1MGPRAG TYPE DEBRIE WRAPPED ON CCTV CABLE
0AMH1:45AM
2SSSBLISTERING PEELING CONCRETE
599.3SAMSEVERE AGG
1049SAMSEVERE AGG
4IW
15.8SAMSEVERE AGG
39.7SAMSEVERE AGG
2MGOCONCRETE BEAM AT 12:00 MISSING SEVERE AGG AND FALLING APART START
412.5SAMSEVERE AGG
1049SSSBLISTERING PEELING CONCRETE
165.7SAMSEVERE AGG
2MGOMAG COAT 85% START
1049DAGS
2SAMSEVERE AGG
882.3SAMSEVERE AGG
1049.7AMH3:05AM
110.3SAMCONCRETE BEAM FALLING APART
1010.2MGODEBRIE ON CABLE

Properties (6)

custom_field_three
SEVERE AGG MISSING
custom_field_two
2
customer
LACSD
datetime
2020-09-11T01:17:05-07:00
documentation
MARTIN,OLIVER 111-BARR,CASTILLO
is_lateral_inspection
false