Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 12, 2020, 08:31 AM
  • 18 0827_18 0826_08122020_013707.mp4

Date
08/12/2020
W/O
844412
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00707
PipeID
P14690
Time
1:31 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7953
Sewer Name
SO WHITTIER OUTFALL TR, SECT 5
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
20
Purpose
Routine Assessment
Project
RFIR_WO_844412_TV18119_AUG2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0827
Downstream MH
18 0826
Dir. of Survey
Downstream
Length Surveyed
94.1 ft.
Total Length
94.1 ft.
Structural Index
3
Structural Quick
4B34
Structural Rating
104
O&M Index
2
O&M Quick
2C00
O&M Rating
36
Overall Index
3
Overall Quick
Overall Rating
140
Pipe schematic from manhole 18 0827 to 18 0826
MH: 18 0827MH: 18 0826downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 08272 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start21.8 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start32.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"36.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"81.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"85.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"92 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish92 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish92.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish92.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish92.6 ft. MGO - General Observation - ROACHES @ MH94.1 ft. AMH - Downstream Manhole, Survey Ends - 18 082694.1 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE

Observation photos (4)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    21.8 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - ROACHES @ MH

    92.6 ft. - General Observation - ROACHES @ MH

Observations (18)

DistanceCodeObservation
36.2TFC
92SSS
2CM
21.8FM
94.1AMH18 0826
85.3TFC
92.6DAGS
92CM
92.6FM
0MWL
92.6MGOROACHES @ MH
2DAGS
81.8TFC
0MWM
32.3TFA
0AMH18 0827
2SSS
94.1MGOCONN @ MH 3 O'CLOCK/ACTIVE

Properties (7)

additional_info
SC411743
custom_field_three
MULTIPLE FRACTURES/CRACKS
custom_field_two
2
customer
1
datetime
2020-08-12T01:31:15-07:00
documentation
PRO PIPE
is_lateral_inspection
false