Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 12, 2020, 07:22 AM
  • 18 0812_18 0783_08122020_003343.mp4

Date
08/12/2020
W/O
844412
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00707
PipeID
P14675
Time
12:22 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7953
Sewer Name
SO WHITTIER OUTFALL TR, SECT 5
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
20
Purpose
Routine Assessment
Project
RFIR_WO_844412_TV18119_AUG2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0783
Downstream MH
18 0812
Dir. of Survey
Upstream
Length Surveyed
200.1 ft.
Total Length
200.1 ft.
Structural Index
4
Structural Quick
4G21
Structural Rating
158
O&M Index
2
O&M Quick
2G00
O&M Rating
78
Overall Index
3
Overall Quick
Overall Rating
236
Pipe schematic from manhole 18 0783 to 18 0812
MH: 18 0783MH: 18 0812upstream0 ft. AMH - Upstream Manhole, Survey Ends - 18 08121 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish1.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish198.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start198.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start200.1 ft. MGO - General Observation - CONN @ MH 6 O'CLCOK/ACTIVE200.1 ft. MWM - Water Mark, 25 %of cross sectional area200.1 ft. AMH - Downstream Manhole, Survey Begins - 18 0783200.1 ft. MWL - Water Level, 20 %of cross sectional area200.1 ft. MGO - General Observation - CONN @ MH 3 O' CLOCK/ACTIVE

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
0MGOCONN @ MH 6 O'CLCOK/ACTIVE
0MWM
0AMH18 0783
2DAGS
0MWL
200.1AMH18 0812
199FM
0MGOCONN @ MH 3 O' CLOCK/ACTIVE
2FM
199.1DAGS

Properties (5)

additional_info
SC411743
customer
1
datetime
2020-08-12T00:22:39-07:00
documentation
PRO PIPE
is_lateral_inspection
false