- Date
- 08/03/2020
- W/O
- 844347
- Weather
- Dry
- Operator/Surveyor
- S. LOPEZ
- Sewer ID
- Z00790
- PipeID
- P17343
- Time
- 11:45 PM
- Certificate
- U-0720-70309212
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K7896
- Sewer Name
- BASE LINE TRUNK
- City
- GLENDORA
- Loc. details
- Main Highway - Suburban/Rural
- Location Code
- B
- Use of Sewer
- Sanitary Sewer
- District
- District 22
- Page No.
- 12
- Purpose
- Routine Assessment
- Project
- RFIR_WO_844347_TV22002_AUG2020
- Sewer Type
- Gravity
- Material
- NRCP
- Shape
- Circular
- Height
- 15 in.
- Width
- 15 in.
- Upstream MH
- 22 0972
- Downstream MH
- 22 0973
- Dir. of Survey
- Upstream
- Length Surveyed
- 227.9 ft.
- Total Length
- 227.9 ft.
- Structural Index
- 3
- Structural Quick
- 3H2H
- Structural Rating
- 225
- O&M Index
- 2
- O&M Quick
- 2200
- O&M Rating
- 4
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 229
Pipe schematic from manhole 22 0972 to 22 0973 Observation photos (3)

0 ft. - General Observation - ROACHES @ MH

4 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

226.6 ft. - General Observation - ROACHES @ MH