- Date
- 07/06/2020
- W/O
- 839009
- Weather
- Dry
- Operator/Surveyor
- J. BUENROSTRO
- Sewer ID
- Z00705
- PipeID
- P14357
- Time
- 1:22 AM
- Certificate
- U-715-07000770
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- K7815
- Sewer Name
- SOUTH PLANT OUTFALL TRUNK
- City
- WHITTIER
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 18
- Page No.
- 14
- Purpose
- Routine Assessment
- Project
- RFIR_WO_839009_TV18180_JUL2020
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 21 in.
- Width
- 21 in.
- Upstream MH
- 18 0503
- Downstream MH
- 18 0502
- Dir. of Survey
- Downstream
- Length Surveyed
- 507.1 ft.
- Total Length
- 507.1 ft.
- Structural Index
- 3
- Structural Quick
- 4R3S
- Structural Rating
- 670
- O&M Index
- 2
- O&M Quick
- 2S00
- O&M Rating
- 200
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 870
Pipe schematic from manhole 18 0503 to 18 0502 Observation photos (3)

4.5 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

15.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

36.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start