Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 6, 2020, 10:14 AM
  • 18 0499_18 0498_07062020_032941.mp4

Date
07/06/2020
W/O
839009
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00705
PipeID
P14353
Time
3:14 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7815
Sewer Name
SOUTH PLANT OUTFALL TRUNK
City
WHITTIER
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
14
Purpose
Routine Assessment
Project
RFIR_WO_839009_TV18180_JUL2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
18 0499
Downstream MH
18 0498
Dir. of Survey
Downstream
Length Surveyed
295.8 ft.
Total Length
295.8 ft.
Structural Index
4
Structural Quick
514F
Structural Rating
151
O&M Index
2
O&M Quick
2L12
O&M Rating
132
Overall Index
3
Overall Quick
Overall Rating
283
Pipe schematic from manhole 18 0499 to 18 0498
MH: 18 0499MH: 18 0498downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 04990 ft. MGO - General Observation - ACTIVE CONNECTION IN MH, 9 O' CLOCK0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area3.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start93.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - ACTIVE127.8 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start151.6 ft. RFC - Roots Fine Connection, at 12 o'clock151.6 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6" - ACTIVE159 ft. B - Broken, from 08 to 12 o'clock, within 8 inches of joint: YES201.5 ft. RFJ - Roots Fine Joint, from 03 to 09 o'clock, within 8 inches of joint: YES211.9 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ACTIVE256.9 ft. MWLS - Water Level, Sag in pipe, 10 %of cross sectional area, Start258.5 ft. DSC - Deposits Settled Compacted, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start264.9 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 4" - APPARENTLY ACTIVE293.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish293.3 ft. DSC - Deposits Settled Compacted, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish293.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish293.3 ft. MWLS - Water Level, Sag in pipe, 10 %of cross sectional area, Finish295.8 ft. AMH - Downstream Manhole, Survey Ends - 18 0498

Observation photos (6)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    3.4 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    127.8 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Connection, at 12 o'clock

    151.6 ft. - Roots Fine Connection, at 12 o'clock

  • Broken, from 08 to 12 o'clock, within 8 inches of joint: YES

    159 ft. - Broken, from 08 to 12 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 03 to 09 o'clock, within 8 inches of joint: YES

    201.5 ft. - Roots Fine Joint, from 03 to 09 o'clock, within 8 inches of joint: YES

  • Water Level, Sag in pipe, 10 %of cross sectional area, Start

    256.9 ft. - Water Level, Sag in pipe, 10 %of cross sectional area, Start

Observations (20)

DistanceCodeObservation
293.3FM
211.9TBACTIVE
159B
264.9TFAPPARENTLY ACTIVE
0AMH18 0499
256.9MWLS
201.5RFJ
295.8AMH18 0498
293.3DSC
127.8FM
293.3DAGS
0MGOACTIVE CONNECTION IN MH, 9 O' CLOCK
258.5DSC
93.8TFACTIVE
293.3MWLS
0MWM
151.6RFC
0MWL
3.4DAGS
151.6TBACTIVE

Properties (7)

additional_info
SC411625
custom_field_three
BROKEN, SEVERE FRACTURES
custom_field_two
1
customer
1
datetime
2020-07-06T03:14:06-07:00
documentation
PROPIPE
is_lateral_inspection
false