Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 31, 2020, 06:12 AM
  • 02 0373_02 0372 _07302020_232619.mp4

Date
07/30/2020
W/O
844297
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00250
PipeID
P02688
Time
11:12 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7893
Sewer Name
DOWNEY AVENUE EXTENSION TRUNK
City
PARAMOUNT
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
36
Purpose
Routine Assessment
Project
RFIR_WO_844297_TV02379_AUG2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 0372
Downstream MH
02 0373
Dir. of Survey
Upstream
Length Surveyed
298.9 ft.
Total Length
298.9 ft.
Structural Index
3
Structural Quick
3K2K
Structural Rating
295
O&M Index
2
O&M Quick
2K00
O&M Rating
118
Overall Index
2
Overall Quick
Overall Rating
413
Pipe schematic from manhole 02 0372 to 02 0373
MH: 02 0372MH: 02 0373upstream0 ft. MGO - General Observation - CONN @ MH 3 O' CLOCK/OPEN0 ft. AMH - Upstream Manhole, Survey Ends - 02 03730.9 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/CAPPED0.9 ft. MGO - General Observation - ROACHES @ MH2.7 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish2.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish53.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"98.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"106.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"156.4 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"160.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"202 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"209.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"251.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"251.9 ft. MWL - Water Level, 50 %of cross sectional area258.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"268.9 ft. MWL - Water Level, 40 %of cross sectional area296.9 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start296.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start296.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start298.9 ft. MWL - Water Level, 30 %of cross sectional area298.9 ft. MWM - Water Mark, 35 %of cross sectional area298.9 ft. AMH - Downstream Manhole, Survey Begins - 02 0372

Observation photos (1)

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (24)

DistanceCodeObservation
245.1TFC
47.5TFC
298MGOCONN @ MH 9 O'CLOCK/CAPPED
200.7TFC
89.2TFC
2CM
0MWL
298MGOROACHES @ MH
0MWM
138.3TFC
298.9MGOCONN @ MH 3 O' CLOCK/OPEN
296.2CM
296SSS
2SSS
296DAGS
2DAGS
298.9AMH02 0373
142.5TBA
96.9TFC
192TFA
47MWL
30MWL
0AMH02 0372
40.4TFA

Properties (7)

additional_info
SC411733
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2020-07-30T23:12:57-07:00
documentation
PRO PIPE
is_lateral_inspection
false