Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 31, 2020, 05:26 AM
  • 02 0369_02 0368A _07302020_223543.mp4

Date
07/30/2020
W/O
844297
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00250
PipeID
P02684
Time
10:26 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7893
Sewer Name
DOWNEY AVENUE EXTENSION TRUNK
City
PARAMOUNT
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
02
Purpose
Routine Assessment
Project
RFIR_WO_844297_TV02379_AUG2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 0369
Downstream MH
02 0368A
Dir. of Survey
Downstream
Length Surveyed
126.1 ft.
Total Length
126.1 ft.
Structural Index
3
Structural Quick
3D2D
Structural Rating
120
O&M Index
2
O&M Quick
4131
O&M Rating
63
Overall Index
2
Overall Quick
Overall Rating
183
Pipe schematic from manhole 02 0369 to 02 0368A
MH: 02 0369MH: 02 0368Adownstream0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MGO - General Observation - ROACHES @ MH0 ft. AMH - Upstream Manhole, Survey Begins - 02 03690 ft. MWM - Water Mark, 35 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start10.1 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6"25.3 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 4", 4" - UNKNOWN44.4 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6"75.9 ft. TBD - Tap Break-In Defective, at 10 o'clock, -, , within 8 inches of joint: YES, 4", 6" - CAPPED/BROKEN CONN115.1 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6"121.7 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6"124 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish124.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish124.1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish126.1 ft. MGO - General Observation - ROACHES @ MH126.1 ft. AMH - Downstream Manhole, Survey Ends - 02 0368A

Observation photos (4)

  • General Observation - ROACHES @ MH

    0 ft. - General Observation - ROACHES @ MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - ROACHES @ MH

    126.1 ft. - General Observation - ROACHES @ MH

Observations (18)

DistanceCodeObservation
121.7TBC
75.9TBDCAPPED/BROKEN CONN
0MWL
2DAGS
2CM
10.1TBC
0MGOROACHES @ MH
124.1DAGS
0AMH02 0369
0MWM
124.1CM
115.1TBC
2SSS
25.3TBUNKNOWN
124SSS
126.1MGOROACHES @ MH
44.4TBC
126.1AMH02 0368A

Properties (6)

additional_info
SC411733
custom_field_two
3
customer
1
datetime
2020-07-30T22:26:33-07:00
documentation
PRO PIPE
is_lateral_inspection
false