Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 10, 2020, 11:45 AM
  • 05 1390_05 1389_08102020_050040.mp4

Date
08/10/2020
W/O
844677
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00487
PipeID
P06610
Time
4:45 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7943
Sewer Name
MONETA TRUNK
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_844677_TV05074_AUG2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
8 in.
Upstream MH
05 1390
Downstream MH
05 1389
Dir. of Survey
Downstream
Length Surveyed
338.4 ft.
Total Length
338.4 ft.
Structural Index
3
Structural Quick
4J3L
Structural Rating
551
O&M Index
2
O&M Quick
2P00
O&M Rating
172
Overall Index
3
Overall Quick
Overall Rating
723
Pipe schematic from manhole 05 1390 to 05 1389
MH: 05 1390MH: 05 1389downstream0 ft. MGO - General Observation - ROACHES @ MH0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 13900 ft. MGO - General Observation - CONN @ MH 9 O' CLOCK/ACTIVE2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start69.3 ft. FM - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start73.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"124.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"160.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN209.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"252 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start258 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 02 to 05 o'clock, , within 8 inches of joint: YES, Start260.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6"261 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 02 to 05 o'clock, , within 8 inches of joint: YES, Finish296.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6"330.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"336 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish336 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish336 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish338 ft. MGO - General Observation - ROACHES @ MH338 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Finish338.4 ft. FM - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish338.4 ft. AMH - Downstream Manhole, Survey Ends - 05 1389

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    69.3 ft. - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

Observations (26)

DistanceCodeObservation
336CM
338.4FM
252DAGS
338MGOROACHES @ MH
336SSS
0MGOROACHES @ MH
0MWL
338DAGS
261DAGS
258DAGS
69.3FM
330.2TFC
160.6TFOPEN
2DAGS
260.6TFA
296.6TFA
124.9TFC
336DAGS
0MWM
3CM
338.4AMH05 1389
0AMH05 1390
0MGOCONN @ MH 9 O' CLOCK/ACTIVE
73.7TFC
209.3TFC
2SSS

Properties (7)

additional_info
SC411805
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2020-08-10T04:45:34-07:00
documentation
PROPIPE
is_lateral_inspection
false