Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 11, 2020, 04:26 AM
  • 05 1388_05 1387_08102020_214209.mp4

Date
08/10/2020
W/O
844677
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00487
PipeID
P06608
Time
9:26 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7945
Sewer Name
MONETA TRUNK
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_844677_TV05074_AUG2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
8 in.
Upstream MH
05 1388
Downstream MH
05 1387
Dir. of Survey
Downstream
Length Surveyed
340.2 ft.
Total Length
340.2 ft.
Structural Index
3
Structural Quick
3L2L
Structural Rating
335
O&M Index
3
O&M Quick
4222
O&M Rating
12
Overall Index
3
Overall Quick
Overall Rating
347
Pipe schematic from manhole 05 1388 to 05 1387
MH: 05 1388MH: 05 1387downstream0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/UNKNOWN0 ft. AMH - Upstream Manhole, Survey Begins - 05 13880 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start5.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start15.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN39.2 ft. IR - Infiltration Runner, from 12 to 05 o'clock, within 8 inches of joint: YES39.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 05 o'clock, , within 8 inches of joint: YES40.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6"78.6 ft. RBL - Roots Ball Lateral, at 10 o'clock, 65 %78.6 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 4", 4" - 95% ROOTS/GREASE-LATERAL/ACTIVE160 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"195.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN247.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN298.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN338 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish340.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish340.2 ft. AMH - Downstream Manhole, Survey Ends - 05 1387

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (19)

DistanceCodeObservation
5.8CM
298.8TFOPEN
247.2TFOPEN
195.7TFOPEN
0MGOCONN @ MH 3 O'CLOCK/UNKNOWN
0AMH05 1388
340.2CM
0MWL
2SSS
338SSS
78.6RBL
78.6TFD95% ROOTS/GREASE-LATERAL/ACTIVE
40.1TFA
15.2TFOPEN
160TFC
340.2AMH05 1387
39.2IR
39.2DAGS
0MWM

Properties (7)

additional_info
SC411807
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2020-08-10T21:26:56-07:00
documentation
PROPIPE
is_lateral_inspection
false