Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 11, 2020, 05:38 AM
  • 05 1384_05 1383_08102020_225302.mp4

Date
08/10/2020
W/O
844677
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00487
PipeID
P06604
Time
10:38 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7945
Sewer Name
MONETA TRUNK
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_844677_TV05074_AUG2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
8 in.
Upstream MH
05 1384
Downstream MH
05 1383
Dir. of Survey
Downstream
Length Surveyed
296.4 ft.
Total Length
296.4 ft.
Structural Index
3
Structural Quick
413K
Structural Rating
294
O&M Index
2
O&M Quick
312K
O&M Rating
119
Overall Index
2
Overall Quick
Overall Rating
413
Pipe schematic from manhole 05 1384 to 05 1383
MH: 05 1384MH: 05 1383downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 13840 ft. MGO - General Observation - ROACHES @ MH0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start49.4 ft. DAGS - Deposits Attached Grease, 15 %of cross sectional area, from 12 to 05 o'clock, , within 8 inches of joint: YES50.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6"66.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6"133 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN199.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN243.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"293 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES293 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish294 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish294 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish296.4 ft. AMH - Downstream Manhole, Survey Ends - 05 1383296.4 ft. MGO - General Observation - CONN @ MH 3 O' CLOCK/ACTIVE296.4 ft. MGO - General Observation - CONN @ MH 9 O' CLOCK/ACTIVE

Observation photos (3)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 15 %of cross sectional area, from 12 to 05 o'clock,  , within 8 inches of joint: YES

    49.4 ft. - Deposits Attached Grease, 15 %of cross sectional area, from 12 to 05 o'clock, , within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    293 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (20)

DistanceCodeObservation
293FM
2DAGS
0AMH05 1384
296.4AMH05 1383
0MGOROACHES @ MH
296.4MGOCONN @ MH 3 O' CLOCK/ACTIVE
294DAGS
49.4DAGS
293CM
3.5CM
0MWL
199.5TFOPEN
243.1TFC
296.4MGOCONN @ MH 9 O' CLOCK/ACTIVE
133TFOPEN
294SSS
66.2TFA
2SSS
0MWM
50.3TFA

Properties (7)

additional_info
SC411807
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2020-08-10T22:38:31-07:00
documentation
PROPIPE
is_lateral_inspection
false