Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 11, 2020, 05:56 AM
  • 05 1383_05 1382_08102020_230014.mp4

Date
08/10/2020
W/O
844677
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00487
PipeID
P06603
Time
10:56 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7945
Sewer Name
MONETA TRUNK
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_844677_TV05074_AUG2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
8 in.
Upstream MH
05 1383
Downstream MH
05 1382
Dir. of Survey
Downstream
Length Surveyed
27.5 ft.
Total Length
27.5 ft.
Structural Index
3
Structural Quick
3525
Structural Rating
25
O&M Index
2
O&M Quick
2500
O&M Rating
10
Overall Index
2
Overall Quick
Overall Rating
35
Pipe schematic from manhole 05 1383 to 05 1382
MH: 05 1383MH: 05 1382downstream0 ft. MGO - General Observation - CONN @ MH 3 O' CLOCK/ACTIVE0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 9 O' CLOCK/ACTIVE0 ft. AMH - Upstream Manhole, Survey Begins - 05 13830 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start25 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish25 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish27 ft. MGO - General Observation - ROACHES @ MH27.5 ft. AMH - Downstream Manhole, Survey Ends - 05 138227.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
2DAGS
27MGOROACHES @ MH
27.5AMH05 1382
0MGOCONN @ MH 3 O' CLOCK/ACTIVE
0MWL
25DAGS
25SSS
0MGOCONN @ MH 9 O' CLOCK/ACTIVE
0AMH05 1383
0MWM
2.1CM
27.5CM
2SSS

Properties (7)

additional_info
SC411807
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2020-08-10T22:56:34-07:00
documentation
PROPIPE
is_lateral_inspection
false