Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 12, 2020, 08:46 AM
  • 05 1371_05 1326_08122020_020006.mp4

Date
08/12/2020
W/O
844677
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00487
PipeID
P06590
Time
1:46 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7947
Sewer Name
MONETA TRUNK
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_844677_TV05074_AUG2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
05 1371
Downstream MH
05 1326
Dir. of Survey
Downstream
Length Surveyed
333.4 ft.
Total Length
333.4 ft.
Structural Index
3
Structural Quick
413L
Structural Rating
334
O&M Index
2
O&M Quick
2F00
O&M Rating
68
Overall Index
2
Overall Quick
Overall Rating
402
Pipe schematic from manhole 05 1371 to 05 1326
MH: 05 1371MH: 05 1326downstream0 ft. MGO - General Observation - CONN @ MH 3 O' CLOCK/ACTIVE0 ft. AMH - Upstream Manhole, Survey Begins - 05 13710 ft. MGO - General Observation - CONN @ MH 9 O' CLOCK/OPEN0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - ROACHES @ MH2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start17.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"70.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"121.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"171 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start172.3 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN172.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"229.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"283.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"331 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish331 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish331 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish333.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish333.4 ft. FM - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES333.4 ft. AOC - Drop Connection, Survey Ends - 05 1326

Observation photos (3)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

    172.3 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

  • Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

    333.4 ft. - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

Observations (23)

DistanceCodeObservation
17.5TFC
172.3TBOPEN
331SSS
0MGOCONN @ MH 3 O' CLOCK/ACTIVE
2DAGS
333.4CM
172.3TFA
2SSS
0AMH05 1371
2CM
171DAGS
331DAGS
331DAGS
283.4TFC
333.4FM
229.7TFC
0MGOCONN @ MH 9 O' CLOCK/OPEN
121.1TFC
333.4AOC05 1326
0MWM
0MWL
0MGOROACHES @ MH
70.5TFC

Properties (7)

additional_info
SC411809
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2020-08-12T01:46:42-07:00
documentation
PROPIPE
is_lateral_inspection
false