Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 10, 2020, 08:14 AM
  • 05 1398_05 1397_08102020_014753.mp4

Date
08/10/2020
W/O
844699
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00487
PipeID
P06619
Time
1:14 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7944
Sewer Name
MONETA TRUNK
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
18
Purpose
Routine Assessment
Project
RFIR_WO_844699_TV05336_AUG2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
18 in.
Upstream MH
05 1398
Downstream MH
05 1397
Dir. of Survey
Downstream
Length Surveyed
329.4 ft.
Total Length
329.4 ft.
Structural Index
3
Structural Quick
413L
Structural Rating
329
O&M Index
2
O&M Quick
2L00
O&M Rating
130
Overall Index
2
Overall Quick
Overall Rating
459
Pipe schematic from manhole 05 1398 to 05 1397
MH: 05 1398MH: 05 1397downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 13980 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - ROACHES @ MH0 ft. MGO - General Observation - CONN @ MH 9 O' CLOCK/ACTIVE0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start66.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"95.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN155 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"204.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN239.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"291.1 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES291.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"327 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish327 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish328.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish329.4 ft. MGO - General Observation - CONN @ MH 9 O' CLOCK/ACTIVE329.4 ft. AMH - Downstream Manhole, Survey Ends - 05 1397329.4 ft. MGO - General Observation - CONN @ MH 3 O' CLOCK/OPEN

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    291.1 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

Observations (21)

DistanceCodeObservation
327SSS
0AMH05 1398
328.8CM
291.1FM
3.8CM
95.6TFOPEN
0MWL
239.9TFC
0MGOROACHES @ MH
66.3TFC
329.4MGOCONN @ MH 9 O' CLOCK/ACTIVE
327DAGS
2DAGS
0MGOCONN @ MH 9 O' CLOCK/ACTIVE
2SSS
329.4AMH05 1397
291.4TFC
155TFC
0MWM
329.4MGOCONN @ MH 3 O' CLOCK/OPEN
204.1TFOPEN

Properties (7)

additional_info
SC411806
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2020-08-10T01:14:23-07:00
documentation
PROPIPE
is_lateral_inspection
false