Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 26, 2020, 09:10 AM
  • H 0608_H 0607 _08262020_021450.mp4

Date
08/26/2020
W/O
844691
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00190
PipeID
P11029
Time
2:10 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7967
Sewer Name
JOINT OUTFALL H - UNIT 8G
City
WEST COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
24
Purpose
Routine Assessment
Project
RFIR_WO_844691_TV15150_AUG2020
Sewer Type
Siphon
Material
Reinforced Concrete Pipe
Shape
Circular
Height
42 in.
Width
42 in.
Upstream MH
H 0608
Downstream MH
H 0607
Dir. of Survey
Downstream
Length Surveyed
2 ft.
Total Length
2 ft.
Structural Index
3
Structural Quick
5131
Structural Rating
10
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
12
Pipe schematic from manhole H 0608 to H 0607
MH: H 0608MH: H 0607downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 06080 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES2 ft. MGO - General Observation - BROKEN REINFORCEMENT - "BOWING" AWAY FROM WALL - 1 O'CLK. - @ "JOINT END" OF DOWN LEG OF SIPHON2 ft. MSA - Survey Abandoned - VIEW OF DOWNLEG OF U/S SIPHON.2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES

Observation photos (5)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Survey Abandoned - VIEW OF DOWNLEG OF U/S SIPHON.

    2 ft. - Survey Abandoned - VIEW OF DOWNLEG OF U/S SIPHON.

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (9)

DistanceCodeObservation
2SAP
2MGOBROKEN REINFORCEMENT - "BOWING" AWAY FROM WALL - 1 O'CLK. - @ "JOINT END" OF DOWN LEG OF SIPHON
0MWL
2MSAVIEW OF DOWNLEG OF U/S SIPHON.
2SRV
0AMHH 0608
0MWM
2DAGS
2SSS

Properties (8)

additional_info
SC411857
custom_field_three
BROKEN-VISIBLE REINFORCMNT./PROJCTNG. AGG./SPALNG.
custom_field_two
1
customer
1
datetime
2020-08-26T02:10:48-07:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
27198