Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 2, 2020, 09:40 AM
  • C 0098_C 0097_922020_040639.mp4

Date
09/02/2020
W/O
0834128
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00122
PipeID
P09565
Time
2:40 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1554
Sewer Name
C JOINT OUTFALL C - UNIT 3C
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
24
Purpose
Capital Improvement Program Assesment
Project
20200901MDM_JOINT_OUTFALL_C_UNIT_3C
Material
Reinforced Concrete Pipe
Shape
Circular
Height
57 in.
Upstream MH
C 0098
Downstream MH
C 0097
Dir. of Survey
Downstream
Length Surveyed
680.8 ft.
Total Length
680.8 ft.
Structural Index
4
Structural Quick
4521
Structural Rating
22
O&M Index
2
O&M Quick
3124
O&M Rating
11
Overall Index
3
Overall Quick
Overall Rating
33
Pipe schematic from manhole C 0098 to C 0097
MH: C 0098MH: C 0097downstream0 ft. AMH - Upstream Manhole, Survey Begins - 4:10AM0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. MGO - General Observation - RAISED CONCRET BEAM 12:00 FALLING APART START2 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. MGO - General Observation - MAG COAT 95% START 10:00 TO 2:002 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE34.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start85.4 ft. SAM - Surface Aggregate Missing, from 12 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG85.4 ft. SAM - Surface Aggregate Missing, from 02 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG151.9 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 01 to 04 o'clock, , within 8 inches of joint: YES295.1 ft. SAM - Surface Aggregate Missing, from 12 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG345.3 ft. IW - Infiltration Weeper, from 08 to 10 o'clock, within 8 inches of joint: YES446.8 ft. MGO - General Observation - CONCRETE BEAM FALLING APART468.2 ft. ID - Infiltration Dripper, from 09 to 03 o'clock, within 8 inches of joint: YES607.7 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 07 to 09 o'clock, , within 8 inches of joint: NO624.4 ft. SAM - Surface Aggregate Missing, from 10 to 12 o'clock, within 8 inches of joint: NO - SEVERE AGG660.6 ft. MGO - General Observation - DEBRIE ON CABLE680.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE680.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish680.2 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - SEVRE AGG680.2 ft. MGO - General Observation - CONCRETE BEAM AT 12:00 FALLING APART FINISH680.8 ft. AMH - Downstream Manhole, Survey Begins - 5:00AM

Observation photos (14)

  • General Observation - RAISED CONCRET BEAM 12:00 FALLING APART START

    2 ft. - General Observation - RAISED CONCRET BEAM 12:00 FALLING APART START

  • Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • General Observation - MAG COAT 95% START 10:00 TO 2:00

    2 ft. - General Observation - MAG COAT 95% START 10:00 TO 2:00

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    34.9 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Missing, from 12 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

    85.4 ft. - Surface Aggregate Missing, from 12 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Aggregate Missing, from 02 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

    85.4 ft. - Surface Aggregate Missing, from 02 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 01 to 04 o'clock,  , within 8 inches of joint: YES

    151.9 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 01 to 04 o'clock, , within 8 inches of joint: YES

  • Surface Aggregate Missing, from 12 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

    295.1 ft. - Surface Aggregate Missing, from 12 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Infiltration Weeper, from 08 to 10 o'clock, within 8 inches of joint: YES

    345.3 ft. - Infiltration Weeper, from 08 to 10 o'clock, within 8 inches of joint: YES

  • General Observation - CONCRETE BEAM FALLING APART

    446.8 ft. - General Observation - CONCRETE BEAM FALLING APART

  • Deposits Attached Grease, 10 %of cross sectional area, from 07 to 09 o'clock,  , within 8 inches of joint: NO

    607.7 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 07 to 09 o'clock, , within 8 inches of joint: NO

  • Surface Aggregate Missing, from 10 to 12 o'clock, within 8 inches of joint: NO - SEVERE AGG

    624.4 ft. - Surface Aggregate Missing, from 10 to 12 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • General Observation - DEBRIE ON CABLE

    660.6 ft. - General Observation - DEBRIE ON CABLE

Observations (23)

DistanceCodeObservation
0AMH4:10AM
680.2SSSBLISTERING PEELING CONCRETE
607.7DAGS
468.2ID
446.8MGOCONCRETE BEAM FALLING APART
2MGORAISED CONCRET BEAM 12:00 FALLING APART START
295.1SAMSEVERE AGG
0MWM
624.4SAMSEVERE AGG
680.2DAGS
85.4SAMSEVERE AGG
34.9DAGS
660.6MGODEBRIE ON CABLE
680.8AMH5:00AM
0MWL
2SAMSEVERE AGG
680.2SAMSEVRE AGG
2MGOMAG COAT 95% START 10:00 TO 2:00
151.9DAE
680.2MGOCONCRETE BEAM AT 12:00 FALLING APART FINISH
2SSSBLISTERING PEELING CONCRETE
345.3IW
85.4SAMSEVERE AGG

Properties (6)

custom_field_three
SEVERE AGG MISSING
custom_field_two
2
customer
LACSD
datetime
2020-09-02T02:40:29-07:00
documentation
MARTIN,OLIVER 111,BARR,CASTILLO
is_lateral_inspection
false