Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 7, 2020, 07:19 AM
  • 05 2343_05 2342_07072020_003041.mp4

Date
07/07/2020
W/O
839466
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00440
PipeID
P07456
Time
12:19 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7902
Sewer Name
EL NIDO RELIEF TRUNK
City
REDONDO BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
23
Purpose
Routine Assessment
Project
WO_839466_TV05024_JUL2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
12 in.
Upstream MH
05 2343
Downstream MH
05 2342
Dir. of Survey
Downstream
Length Surveyed
278.6 ft.
Total Length
278.6 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
2
Overall Quick
Overall Rating
3
Pipe schematic from manhole 05 2343 to 05 2342
MH: 05 2343MH: 05 2342downstream0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 23433.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES3.1 ft. RFJ - Roots Fine Joint, at 12 o'clock, within 8 inches of joint: YES248.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6"278.6 ft. AMH - Downstream Manhole, Survey Ends - 05 2342278.6 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (1)

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    3.1 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

Observations (9)

DistanceCodeObservation
3.1CL
278.6AMH05 2342
0MGOCONNECTION AT MH 9 O'CLOCK
0MWL
278.6MGOCONNECTION AT MH 3 O'CLOCK
3.1RFJ
0MWM
248.8TF
0AMH05 2343

Properties (8)

additional_info
SC411761
custom_field_three
NO SEVERE DEFECTS
custom_field_two
4
customer
1
datetime
2020-07-07T00:19:14-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
31994