Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 7, 2020, 07:31 AM
  • 05 2342_05 2341_07072020_004153.mp4

Date
07/07/2020
W/O
839466
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00440
PipeID
P07455
Time
12:31 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7902
Sewer Name
EL NIDO RELIEF TRUNK
City
REDONDO BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
23
Purpose
Routine Assessment
Project
WO_839466_TV05024_JUL2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
8 in.
Upstream MH
05 2342
Downstream MH
05 2341
Dir. of Survey
Downstream
Length Surveyed
305.3 ft.
Total Length
305.3 ft.
Structural Index
2
Structural Quick
3122
Structural Rating
7
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
7
Pipe schematic from manhole 05 2342 to 05 2341
MH: 05 2342MH: 05 2341downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 23420 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK247.5 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"290 ft. CM - Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES291.6 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES296.8 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES305.3 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK305.3 ft. AMH - Downstream Manhole, Survey Ends - 05 2341305.3 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (4)

  • Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    247.5 ft. - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"

  • Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES

    290 ft. - Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    291.6 ft. - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    296.8 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

Observations (11)

DistanceCodeObservation
305.3MGOCONNECTION AT MH 3 O'CLOCK
0MWM
0MWL
0AMH05 2342
291.6CL
290CM
305.3AMH05 2341
0MGOCONNECTION AT MH 3 O'CLOCK
247.5TBA
305.3MGOCONNECTION AT MH 9 O'CLOCK
296.8CL

Properties (7)

additional_info
SC411761
custom_field_two
3
customer
1
datetime
2020-07-07T00:31:16-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
31994