Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 2, 2020, 04:33 AM
  • 05 2339_05 2338_07012020_214027.mp4

Date
07/01/2020
W/O
839466
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00440
PipeID
P07452
Time
9:33 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7901
Sewer Name
EL NIDO RELIEF TRUNK
City
REDONDO BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
23
Purpose
Routine Assessment
Project
WO_839466_TV05024_JUL2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
15 in.
Upstream MH
05 2339
Downstream MH
05 2338
Dir. of Survey
Downstream
Length Surveyed
210.9 ft.
Total Length
210.9 ft.
Structural Index
3
Structural Quick
3421
Structural Rating
14
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
14
Pipe schematic from manhole 05 2339 to 05 2338
MH: 05 2339MH: 05 2338downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 23390 ft. MWL - Water Level, 15 %of cross sectional area4.1 ft. CM - Crack Multiple, from 09 to 10 o'clock, within 8 inches of joint: YES9.3 ft. CM - Crack Multiple, from 08 to 05 o'clock, within 8 inches of joint: YES69.3 ft. CL - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES86.8 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES122.4 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES210.9 ft. AMH - Downstream Manhole, Survey Ends - 05 2338

Observation photos (5)

  • Crack Multiple, from 09 to 10 o'clock, within 8 inches of joint: YES

    4.1 ft. - Crack Multiple, from 09 to 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 05 o'clock, within 8 inches of joint: YES

    9.3 ft. - Crack Multiple, from 08 to 05 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES

    69.3 ft. - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    86.8 ft. - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    122.4 ft. - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES

Observations (9)

DistanceCodeObservation
9.3CM
210.9AMH05 2338
0MWM
0AMH05 2339
4.1CM
122.4FL
69.3CL
86.8FL
0MWL

Properties (8)

additional_info
SC411760
custom_field_three
NO SEVERE DEFECTS
custom_field_two
4
customer
1
datetime
2020-07-01T21:33:31-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
31994