Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 14, 2020, 05:35 AM
  • B 0728A_B 0728_07132020_224917.mp4

Date
07/13/2020
W/O
839013
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00111
PipeID
P09193
Time
10:35 PM
Certificate
U-111-11880
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7876
Sewer Name
JOINT OUTFALL B - UNIT 8H
City
DUARTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
02
Purpose
Routine Assessment
Project
RFIR_WO_839013_TV22165_JUL2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
21 in.
Upstream MH
B 0728A
Downstream MH
B 0728
Dir. of Survey
Downstream
Length Surveyed
342.4 ft.
Total Length
342.4 ft.
Structural Index
4
Structural Quick
4F3E
Structural Rating
232
O&M Index
2
O&M Quick
2M00
O&M Rating
136
Overall Index
3
Overall Quick
Overall Rating
368
Pipe schematic from manhole B 0728A to B 0728
MH: B 0728AMH: B 0728downstream0 ft. AMH - Upstream Manhole, Survey Begins - B 0728A0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MGO - General Observation - CONNECTION IN MH, 9 O' CLOCK0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES AT MH2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start9.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start169 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start169 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish340.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish340.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish342.4 ft. MGO - General Observation - CONNECTION IN MH, 9 O' CLOCK342.4 ft. AMH - Downstream Manhole, Survey Ends - B 0728342.4 ft. MGO - General Observation - COCKROACHES AT MH

Observation photos (5)

  • General Observation - COCKROACHES AT MH

    0 ft. - General Observation - COCKROACHES AT MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    9.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    169 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES AT MH

    342.4 ft. - General Observation - COCKROACHES AT MH

Observations (14)

DistanceCodeObservation
9.2CM
342.4MGOCONNECTION IN MH, 9 O' CLOCK
340.6DAGS
340.6FM
169FM
342.4AMHB 0728
2DAGS
0AMHB 0728A
0MWM
0MGOCONNECTION IN MH, 9 O' CLOCK
342.4MGOCOCKROACHES AT MH
0MWL
169CM
0MGOCOCKROACHES AT MH

Properties (7)

additional_info
SC411715
custom_field_three
MULTIPLE CRACKS/FRACTURES
custom_field_two
2
customer
1
datetime
2020-07-13T22:35:58-07:00
documentation
PRO PIPE
is_lateral_inspection
false