Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 13, 2020, 08:58 AM
  • 08 0230_08 0229 _07132020_024113.mp4

Date
07/13/2020
W/O
839004
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00005
PipeID
P00104
Time
1:58 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7912
Sewer Name
EAST ROAD TRUNK
City
TORRANCE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_839004_TV08112_JUL2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
12 in.
Upstream MH
08 0230
Downstream MH
08 0229
Dir. of Survey
Downstream
Length Surveyed
349.4 ft.
Total Length
349.4 ft.
Structural Index
4
Structural Quick
4100
Structural Rating
4
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
4
Pipe schematic from manhole 08 0230 to 08 0229
MH: 08 0230MH: 08 0229downstream0 ft. AMH - Upstream Manhole, Survey Begins - 08 02300 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 30 %of cross sectional area4.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start32.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"86.6 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"183.6 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"246.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"287.2 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"349.4 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK CAPPED349.4 ft. AMH - Downstream Manhole, Survey Ends - 08 0229349.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
349.4MGOCONNECTION AT MH 9 O'CLOCK CAPPED
4.6FM
0AMH08 0230
246.1TFC
183.6TF
349.4AMH08 0229
349.4FM
32.9TFC
0MWL
86.6TF
287.2TF
0MGOCONNECTION AT MH 9 O'CLOCK
0MWM

Properties (7)

additional_info
SC411771
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2020-07-13T01:58:12-07:00
documentation
PROPIPE
is_lateral_inspection
false