Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 13, 2020, 09:41 AM
  • 08 0229_08 0228 _07132020_025915.mp4

Date
07/13/2020
W/O
839004
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00005
PipeID
P00103
Time
2:41 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7912
Sewer Name
EAST ROAD TRUNK
City
TORRANCE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_839004_TV08112_JUL2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
12 in.
Upstream MH
08 0229
Downstream MH
08 0228
Dir. of Survey
Downstream
Length Surveyed
349.4 ft.
Total Length
349.4 ft.
Structural Index
4
Structural Quick
4131
Structural Rating
7
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
7
Pipe schematic from manhole 08 0229 to 08 0228
MH: 08 0229MH: 08 0228downstream0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK CAPPED0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 02293.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start17.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start96.4 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"193.3 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"273.2 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"323.6 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"349.4 ft. AMH - Downstream Manhole, Survey Ends - 08 0228349.4 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK CAPPED349.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish349.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    17.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
0MGOCONNECTION AT MH 9 O'CLOCK CAPPED
3.4CM
193.3TF
96.4TF
349.4AMH08 0228
17.1FM
349.4MGOCONNECTION AT MH 9 O'CLOCK CAPPED
0MWM
349.4FM
323.6TFC
273.2TF
0MWL
349.4CM
0AMH08 0229

Properties (7)

additional_info
SC411771
custom_field_three
MULTIPLE CRACKS/ FRACTURE'S
custom_field_two
2
customer
1
datetime
2020-07-13T02:41:38-07:00
documentation
PROPIPE
is_lateral_inspection
false