Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 13, 2020, 10:12 AM
  • 08 0227_08 0226_07132020_032219.mp4

Date
07/13/2020
W/O
839004
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00005
PipeID
P00101
Time
3:12 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7912
Sewer Name
EAST ROAD TRUNK
City
TORRANCE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_839004_TV08112_JUL2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
12 in.
Upstream MH
08 0227
Downstream MH
08 0226
Dir. of Survey
Downstream
Length Surveyed
135.6 ft.
Total Length
135.6 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 08 0227 to 08 0226
MH: 08 0227MH: 08 0226downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 02270 ft. MWL - Water Level, 10 %of cross sectional area9.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start43.5 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"53.2 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"112.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"135.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish135.6 ft. AMH - Downstream Manhole, Survey Ends - 08 0226135.6 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    9.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
9.7CM
43.5TFC
0MWM
53.2TF
0AMH08 0227
135.6AMH08 0226
112.9TF
135.6MGOCONNECTION AT MH 3 O'CLOCK
0MWL
135.5CM

Properties (7)

additional_info
SC411771
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2020-07-13T03:12:28-07:00
documentation
PROPIPE
is_lateral_inspection
false